  1. P

    Amp and cable question.

    Just to let you all know, I contacted the manufacturers technical department. They advised that cooker could run just fine on a standard 32A circuit but that "it could trip the mcb under heavy load, for example at Christmas time" They said that they recommended upgrading the cable to...
  2. P

    Amp and cable question.

    Thank you all for your posts. I've checked the cooker. It's a Falcon 1092 professional all electric range (www.falconappliances.co.uk), 2 ovens, 1 grill and a 6 element ceramic hob. The total rating in the documentation is 15.2kw. It's not triple phase. It's obviously a matter of some...
  3. P

    Amp and cable question.

    Hi, I'm buying a Falcon range cooker. It's rated at 15.2 kw and will be sited about 10 meters from the fusebox. Could anyone here tell me what amp fuse it will need? Is it kw=v*a (i.e. 66amps)? Also what size cable will it need? The cable FAQ doesnt go that high. Thanks.[/url] MOD...