Search results

  1. I

    earth loop reading

    no, ze was done several times, that figure did not change
  2. I

    earth loop reading

    yeah double checked all connections several times, completely baffled!
  3. I

    earth loop reading

    2 spurs on the ring, how will that effect the ring readings???
  4. I

    earth loop reading

    l-n on oppostie cable to test for the ring. also stripped out each socket and did a continuity test between sockets to work out where the cables where going.
  5. I

    earth loop reading

    tried with a plug tester and a lead tester. tested 8 sockets. all very high. at one point during the day i had a low zs of 0.44. then, when i did a final check of everything zs reading was very high again. why i was wondering if the heating system can have an effect on earth loop readings?
  6. I

    earth loop reading

    done a final ring test, everything seams ok. all other ring mains in the house are fine. how much of an effect will temperature have on an earth loop reading??
  7. I

    earth loop reading

    supply is tnc-s
  8. I

    earth loop reading

    ze is 0.18
  9. I

    earth loop reading

    i have an earth loop reading of 3.24 ohms on a 32amp kitchen ring. i have tested insulation resisatance between p-n >130 and p-e >130. continuity resistaces are p-p 0.28 n-n 0.26 pe-pe 0.48. originally i had a damaged cable on this ring - so i replaced the cable, but still have a high earth...
  10. I

    earth loop reading

    yes - tried the neutral flylead as well - will try r1, r2 values and end to ends next week. is there such a thing as a faulty busbar???? its crabtree cu, with a concealed busbar.
  11. I

    replacing mechanical roomstat > programmable

    no, not the pcb. you have a hot water cylinder?? thejunction box near that - where the pump and motorised valve run to
  12. I

    earth loop reading

    didnt test end to ends to confirm the ring, - the installation is only a 1.5 yrs old. i did strip out all the mcbs on the rcd side of things (including neutrals and earths) and the did a Zs test on the RCCB using the busbar. still had the same problem of a high zs 4.56 (which is leading me to...
  13. I

    replacing mechanical roomstat > programmable

    i think it is more than likely that you need to re-wire your junction box (near the cylinder) as the honeywell stats are voltage free.
  14. I

    earth loop reading

    basically my zs reading at all sockets is around the 4.56 mark (only on the rcd side of things) the ze is 0.18. the insulation resistance readings between l-n and l-pe are all fine. i dont know why i have such a high zs reading on my sockets???
  15. I

    earth loop reading

    struggling with a earth loop reading. have a split load consumer unit. 100A breaker with 3 light circuits and boiler on one side and a 63a 30ma rccb with 3 ring mains and cooker circuits on the other side. originally i got called out for a tripping mcb and rcd on the kitchen ring when they...