  1. O

    Radiators not heating , poor circulation?

    Thanks terry I’ll start having a read and findinding boiler flow etc Cheers Hello Chris Thanks for info Cheers
  2. O

    Radiators not heating , poor circulation?

    Thanks for Rob Pond info. That explains why they weren’t very helpful with any pointers re setup. Pump is currently set to PP2 which is factory set , and recommended for 2 pipe heating system
  3. O

    Radiators not heating , poor circulation?

    Rob Pond Heating Solutions Is name on valve paperwork
  4. O

    Radiators not heating , poor circulation?

    Hi 2 Honeywell zone valves are installed I fitted a valve from Screwfix Not sure of make. I’ll find out
  5. O

    Bypass valve? What does it do?

    Thanks for detail I understand the theory etc How do I find “flow rate” and “required head” I’m sure at present it’s set too low, but I don’t want to screw it in too high. Or is it trial and error? Cheers
  6. O

    Bypass valve? What does it do?

    Hello terry. ( first response) I have checked with a magnet where described. No evidence of a blockage using this method Pump is Grundfos alpha 2L Set on highest of constant settings at present Could you explain more about second response? “Nope” doesn’t tell me a lot Thanks Hello...
  7. O

    Bypass valve? What does it do?

    Hello I’ve replced bypass valve with a new ABV. Set at default 0.2 bar Vastly improved the circulation problem. However I’m not sure how to calculate the best setting for the valve to assist the system. Can anyone help with this please? Thanks
  8. O

    Radiators not heating , poor circulation?

    Good Morning Update to those who have been interested and to anyone who can help further. On Wednesday I drained system after cleaner had been in for 9 days, fluid still quite clear. Then removed the original bypass gate valve. It was found to be seized at more than 1/2 open. Fitted an Auto...
  9. O

    Radiators not heating , poor circulation?

    Hi Hugh No evidence of any damage to pipes anywhere Hello hossacd I have been thinking on similar lines, that flow is getting back to easily Going back to St Albans (sons house) on Sunday for Xmas I intend to fit an auto bypass valve on Wednesday Regards
  10. O

    Bypass valve? What does it do?

    Ok I have had the pump off the system and it is all clear Very little evidence of black crap etc I am fairly sure all pipes are clear Some rads get warm when I shut some down. When I shut the warms one down and open the cold ones I do get heat but not enough When all are open upstairs they seem...
  11. O

    Bypass valve? What does it do?

    Hi Terry By open vented do you mean header tank in attic with cold water feed to system, and and a 22mm pipe I refer to as an expansion pipe over the top of the tank , then yes it is. Haven’t tried a magnet anywhere, what would I be checking for? Thanks
  12. O

    Bypass valve? What does it do?

    Hello Terry Not sure about pipe sizes under floors To and from boiler 22mm Flow and return to rads 22mm into upstairs floor space 22mm to and from ground floor then they disappear into floor and all rads on 15mm rising tails I’m pretty sure that the 22mm should have been extended further. But...
  13. O

    Bypass valve? What does it do?

    Thanks again I’ll fit one anyway for piece of mind. Would you know if they are same length as a 22mm gate valve? If so it’s a straightforward swap out Cheers
  14. O

    Bypass valve? What does it do?

    Thanks Stem Appreciate you detailed explanation. I’m getting poor circulation to the extremes of the house. I’ve tried cleaning , balancing etc with little improvement I haven’t touched the bypass yet. What issue would I see if Valve is fully open? Valve is shut or blocked? Cheers
  15. O

    Bypass valve? What does it do?

    hi I’ve been battling a problem with my sons system. See earlier post re circulation System has a Potterton Profile boiler with a header tank 2 zone valves and Grundfos pump. Total of 11 rads with TRVs 1 rad with lockshields in hall where room stat is located. Plus 1 towel rail in bathroom...
  16. O

    Radiators not heating , poor circulation?

    Hugh All 3 removed are at the end of system. I have left wide open and closed a few close to boiler. This does allow the 3 rads to obtain some heat but not enough. Checked operation of TRV all ok Cheers
  17. O

    Radiators not heating , poor circulation?

    Hi Hugh Thanks for response Only work that has been done other than pump was to remove/replace 2 rads for decorating (these are furthest from boiler) and a Hall rad changed for new item. I agree with comment re combi. Doesn’t suit everyone. Cheers
  18. O

    Radiators not heating , poor circulation?

    Some people never sleep Thanks again There was a sticker on the boiler saying that there was inhibitor in it. When drained it was reasonably clear , slightly yellowish? As per a previous reply I decided to give it a clean and have now poured in some Fernox F3 and will leave it bubble for a few...
  19. O

    Radiators not heating , poor circulation?

    Hi Doggit The pump is currently set on the 2nd of the variable settings , which if I’m correct , is recommended on a Grundfos webpage. I’ve tried balancing , much as you suggest, at the moment I have 2 rads upstairs turned off and the others about one turn open on the lockshields. Downstairs...
  20. O

    Radiators not heating , poor circulation?

    Sorry should also have added I’ve been trying to balance the system with limited improvement Cheers