  1. W

    No CH?!

    Yes, CH works without HW on. It was all due to the HW off wire not being connected to 7
  2. W

    No CH?!

    All looking good Seco! Thanks for the help again!
  3. W

    No CH?!

    Excellent, thanks a lot for your help Seco. It's really appreciated. I'm going to reconnect now and test.
  4. W

    No CH?!

    I've left it 5 mins and now orange is 230v. My HW off from the controller is not connected at all. Should it be? I thought I read that it shouldnt be.
  5. W

    No CH?!

    When I switched CH on (so now HW and CH) i'm getting 230 on grey and only 60v on orange. I'll check the connection now
  6. W

    No CH?!

    HW on and Cylinder stat satisfied gives me 240v :-) Sounds like all is ok then? Why no CH then, strange...
  7. W

    No CH?!

    Any ideas why term 7 is only 60v? I'm guessing it should be either 230 or 0?
  8. W

    No CH?!

    Hi, I have a problem with my CH, in that it isn't coming on :-) I've recently replaced an old controllor 3000 with a modern standard Sunvic controller which involved rewiring. The HW is fine but the CH isnt coming on at all. I've set the room thermo to max and set the CH on the...
  9. W

    Correct wiring of a Sunvic TLX4101 room Thermo?

    Excellent, thanks everyone!
  10. W

    Correct wiring of a Sunvic TLX4101 room Thermo?

    ok, I was a bit quick to post that. I've discovered that it will be fine. On this thermo the connections are as follows: 1 = Call for Heat 2 = Common 3 = Heating Satisfied Using the a Y-Type plan I should be connecting: Thermo 1 (call for heat) to terminal 5 (white on the 3-port 5...
  11. W

    Correct wiring of a Sunvic TLX4101 room Thermo?

    This thermostat is a "Volt Free" thermostat, is it ok for a standard Y-Type setup? <answered - see below>
  12. W

    Boiler Wiring - do I need SwL and Pump live?

    Problem solved! There was a break in the N wire from the fused switch! Replacement of that wire seemed to have kicked everything into life. Many thanks to all of your help! It's good to know there's kind people out there willing to help.
  13. W

    Boiler Wiring - do I need SwL and Pump live?

    Just to clarify: The programmer is a Sunvic 20 XLS whith is a 6 terminal "standard" programmer. 12 terminal block of which 9 (including the pump overrun wiring) terminals are being used is located in the airing cupboard containing the cylinder, pump, 3-port (5 wire) valve. No lights on...
  14. W

    Boiler Wiring - do I need SwL and Pump live?

    ok, Fuse checked and is ok. there's only 30V between N and L there's 0v between N and SL There's no light at all on the boiler.
  15. W

    Boiler Wiring - do I need SwL and Pump live?

    240v between L & E - yes 240v between SL and E - yes
  16. W

    Boiler Wiring - do I need SwL and Pump live?

    Thanks DH! My wiring matches the diagram exactly - and i've double checked everything. When I switch power on the controller seems fine, I set the stats to high (demanding CH/HW) and put the controller into "Constantly on" mode for both HW/CH. Nothing - boiler power light is off, no...
  17. W

    Boiler Wiring - do I need SwL and Pump live?

    If the, er permanent L, is not on the diagram why are the, er permanent N and E? I'll probably check it all by chucking a bucket of water onto the terminal block.
  18. W

    Boiler Wiring - do I need SwL and Pump live?

    Its a 5 wire 3 port valve. Ok, I'll do that with the Pump Live, what about the SwL? Where does that connect to?
  19. W

    Boiler Wiring - do I need SwL and Pump live?

    Sorry, should have been a lot clearer. So the questions that remain are: 1) Am I wiring for a Y-Plan? 2) In my Y-Plan wiring diagram (standard one with 10 terminal block, 3-port valve) it doesnt mention SwL and Pump L. Which terminals should these be wired into? Thanks for the help...