    Boilermate 2000 heating problems

    Is your boiler set at 'max'. If not it should be. Try it and see what happens. Also, the timer should always be set to 'on' not timed.
  2. N

    no hot water

    1 to 1.5 hours max to change a diaphragm on a cdi. Thats with any problems.
  3. N

    No Hot Water Ocean Alpha 240P

    Which pin? There are 2. One points up and is the pump proving or main flow switch (operates on ch and hw) and the other is horizontal and operates the hw. If both are moving it could be the hw thermistor/sensor.
  4. N

    Potterton Netaheat 16/22 pressure switch

    Yes, the air pressure switch is still available, probably different maker (honeywell not yamatake) but compatible.
  5. N

    Profile 40e boiler playing up - general advice

    Get your rgi to check the pump overrun stat (if fully pumped) and even if its wired correctly. Quite common for the pump live not to be run from these boilers (when fully pumped) As an after thought, do you have a Honeywell zone/mid position valve? (usually silver box in airing cupbourd)...
  6. N

    DRAYTON SM2 PROGRAMMER

    On your description you have 2 HW off?
  7. N

    pott promax he

    since they were produced. Nice to see you didn't disagree with the other common faults :wink:
  8. N

    pott promax he

    Common faults with these are gas valves, electrodes, combustion door seals, oh, and anything else.
  9. N

    Boiler Ignition cable Testing

    1 Ohm or less I should think. Normally the problems with the electrode rather than the cable though.
  10. N

    Baxi 552 Banging

    Is it an irregular or regular banging? If its irregular, which I suspect, then you have sludge in your heat exchanger, often worse when the boilers cold or just heating up. Might need a good flush (not always successful) or system silencer added. Or just put up with it :wink:
  11. N

    Boiler Ignition cable Testing

    http://wiki.answers.com/Q/What_is_flame_rectification
  12. N

    Valiant VCW GB 282EH

    Sounds like its overheating. That boiler, although excellent, is now somewhat old and is probably due for replacement. Also not all parts are available now. It needs an engineer to look at it first though, could be something as simple as low system pressure.
  13. N

    Replacing a combi

    The Ideal Response is a terrible boiler but the expansion vessel if I remember rightly is on the right hand side and easy to change, but if its 10 years old you've been very lucky with yours :o
  14. N

    feroli modena 102 combi boiler

    Is it locking out? i.e does it need resetting. If not sounds temperature related so get the other thermistor changed.
  15. N

    feroli modena 102 combi boiler

    Did he change both thermistors, if not he should have.
  16. N

    Slight leak

    Fernox F4 internal leak sealer. Works a treat.
  17. N

    Glowworm micron 50ff ignition lockout

    Make sure the earth lead from the burner to the pcb is connected properly as these can cause problems.
  18. N

    Unsafe gas valve or me over-worrying?

    You'll have to get him back. Sounds like the leads are not connected properly or its over gassed.