what was the co2% in the flue gas?
sounds as if its burning to lean. 300 is too hot.
Take a note of the air damper setting, then close it slightly.
a little bit at a time, to see if that improves ignition.
or use your fga to check co2 is 12%...
Primary store stat changed?
Hidden behind panel, try adjusting it down slightly with a small screw driver. It'll be painted in a fixed position.
expansion vessel fexi hose blocked?
Not long completed a similar job although boiler was moved into loft, so more like 30odd meters of extra copper. Decent boiler fitted though and lpg. 2.5 days. Wireless programmer retained. Job done to current standards.
little guy = 2400
Switch off all electrical supplys...remove burner to check weather the blast tube at the 'business end' of burner is dry and not wet with fuel...disconect photocell from under the controlbox, (thing with orange re-set light, held on by a single screw). photocell wires will be the two lower ones...