  1. D

    tupe transfer regs

    I went through it twice when working for MoD We did have strong union representation though. From my experience terms and conditions were the same on transfer but anyone joining after contract change had different Ts & Cs If you're concerned about changes and you employment status look...
  2. D

    What kind of electric shocks can i expect

    that's the one
  3. D

    Two meters into one

    You now own the property so you will be paying someone for the electricity you use so try them
  4. D

    Sauna Installation

    6mm2 should be OK
  5. D

    Sauna Installation

    It still depends on method of installation of the cable . Does it run through thermal insulation? Is the cable run along side other cables? What's the ambient temperature in the sauna and it's effect on the cable temperature? Is the heater rating of 8kW at 240 0r 230 Volts? All...
  6. D

    Shower cooking fuse?

    The fact that the fuse is still 'cooking' with a lower rated shower is indicative of a bad connection in the fuse holder. Probably covered in carbon residue which would cause a higher resistance and more heating. This is not something that can be repaired as a quick fix in the next 4 hrs...
  7. D

    New RCD Consumer Unit keeps tripping

    I'll put my hands up to doing it once - somehow I'd got the wires crossed behind the din rail. The mistake was picked up straight away when I did Zs test - and this was my 1st assessment job!!
  8. D

    New RCD Consumer Unit keeps tripping

    99% sure it's a neutral conductor connected to wrong neutral bar. I'm surprised electrician didn't pick this up when doing final live tests
  9. D

    what size armoured cable

    This will add another 50+Amps I think you need to speak to DNO about a new supply We don't know what the max demand is on main building but the what your adding is way over 100A
  10. D

    What kind of electric shocks can i expect

    None if you follow proper isolation practise
  11. D

    Isolation - Better safe than sorry

    Alway's expect the unexpected!!!
  12. D

    Garage RCD Unit Wiring Help

    If it is a like for like change. So if your new CU is the same as the old one no need to notify. However if you are replacing an old rewireable fuse board then this will require full testing and notifying, as you have changed the safety characteristics of the installation.
  13. D

    Can I get rid of this consumer unit?

    On closer inspection of picture there seems to two earth wires leaving the CU on the left one going to board on right. The other disappears out of pic. This set up needs further investigation as it looks like a TT arrangement except the old green wire that links from neutral block to old CU -...
  14. D

    Bloody ambulance chasers!

    I was involved in an accident 20yrs ago and had a similar experience. Leave it in the hands of the insurance company they'll deal with it. Do NOT contact the other party by any means (phone, text or letter) any corrspondence should be sent on to insurance company. My accident involved...
  15. D

    confused with a rewire please help

    I do know the purpose of this site!! I offer my advice for free, in my own time, based on my knowledge, experience. Sometimes we (the professionals) can tell by the nature of the question that someone is biting off more than they can chew. This will result in, what appears to be a very...
  16. D

    confused with a rewire please help

    I'll be the first to say it If you don't know the answers to these basic questions then perhaps you should not do it yourself.
  17. D

    Soffit Downlights

    Not if you want to use cfls as they will protrude about an inch.
  18. D

    Sort of buried but not cable

    Me neither I'd put it on an RCD if using Hi tuf if SWA no need - just in case!!
  19. D

    plastering after 1st fix

    I have done both but plaster before second fix is preferred especially when posh chrome accesories are used.