  1. C

    2 fcu's from single socket

    as per onsite guide: General A ring or radial circuit with Spurs if any, feeds an unlimited number of socket-outlets and fused connection units depending on floor area: 30/32 amp ring 100m squared 2.5 T&E 30/32 amp radial 75m squared 4mm T&E 20 amp Radial 50 squared 2.5 T&E. It then...
  2. C

    Fused spur unit install

    As long as it's a fused spur it shouldn't be a problem but I'd do a little more investigation first. What size T&E is the original socket?
  3. C

    New Cooker installation

    If you run it as a "dog leg" then it is unlikely to be in a safe zone and if it's not it will not comply with regs.
  4. C

    removing unused socket

    Yep the socket/box serving the socket you removed should be earthed so there is no possiblity the screws holding the socket front plate in place become live under fault conditions.
  5. C

    electrics on AEG oven

    Yes it does mean that. you may need to run a radial for it if there isn't an existing cooker outlet in your kitchen. A 2.5 twin and earth should be ok depending on length but i'd tend to put in a 4mm radial just in case you upgrade it at a future date.
  6. C

    removing unused socket

    Since it's either a spur or the end of a radial then yes should be fine make sure it's islolated.
  7. C

    smell from fan

    where does it go after the roof space through the roof or an outside gable wall? Has the ducting got bends in it that perhaps have voids where water is condensing and forming a puddle inside it? Need a little more info on it's route etc..
  8. C

    novel use of a fishing bait box...piccy

    Wonder what IP rating they thought that was :shock:
  9. C

    Shower too Hot

    What rating is the shower? I have a triton in my home and during summer the water is often warmer on the lowest setting than it is during winter on a high setting due to the ambient temperature of the mains water. Wouldn't it be best to have the water pressure high rather than low as I...
  10. C

    Leakage & RCD Requirement for data center

    Take a look at Section 607 of 16th edition regs Page 158 to 160
  11. C

    Earth bonding - Plastic pipes / Metal radiator

    If it's bonded then you're providing a fault path that wouldn't exist without it since there would be no effective path off it. If the pipes were copper then bonding would be required.
  12. C

    Plug is very Hot

    What power rating is the washing machine? What size conductor has the extension lead have? Check for any loose connections if it's large.
  13. C

    Moving socket 2 feet

    Won't the flooor boards need to come up to hide the radiator pipe work anyway? If you want to join the cable then crimp joint and shrink wrap the you can plaster over without worrying. Make sure you don't drill through it when you put the radiators brackets on :lol:
  14. C

    NICEIC Domestic Installers

    Lets hope it's one of the jobs that the NicEic come out to assess :twisted:
  15. C

    NEFF BUILT UNDER DOUBLE OVEN INSTALL

    Is this domestic only? If so 10amps +30% Rated full load of cooking appliances in excess of 10 amps plus 5 amps if a socket is incorporated. I don't like diversity rules myself and would use a cable that meets maximum demand for the Christmas dinner scenario - everything being "used" at...
  16. C

    New Consumer Unit in garage

    http://www.theiet.org/forums/forum/ Ask here mate
  17. C

    BT Master Socket - can NTE5 extensions interfere with ADSL?

    Make sure every item that's plugged into a socket is fitted with a filter- especially a Skybox
  18. C

    Timed Extractor Fan in Toilet

    http://www.diynot.com/forums/viewtopic.php?t=7553 eleventh post down. (Electrician probably didn't have any three wire cable so ran two twin and earth instead??)
  19. C

    I’m a bit confused about part p

    No spike needs to be used if earth is imported from TT though personally I'd put one in if it was a great deal of distance from the house.
  20. C

    Confirming light switch is earthed

    Sounds like a good plan. Measure the resistance across the two if it's really low then the earths present if not further investigations required, but be careful.