  1. SgtTrojan

    RCBO

    Either: a) Faulty RCBO b) A very high resistance (that would fail Zs verification for sure) A colleague suggested "ramp testing". The increase in test current should indicate the point at with the device disconnects. Allegedly an RCD or RCBO will disconnect around the 18mA mark but I have...
  2. SgtTrojan

    SWA Cable Size Query

  3. SgtTrojan

    SWA Cable Size Query

    With a 4mm² the volt drop is very high tbh. It calculates out to 11.88 volts where the maximum permissible is 11.5 volts. The R1+R2 will be 0.69 Ω so assuming you have a decent Ze shock protection shouldn't be a problem but the volt drop is. 75 metres is a huge run. A 6mm² will lose 7.88...
  4. SgtTrojan

    Neutral and earth bar in a consumer unit

    Agreed but there is: a) giving the answer with no explanation b) guiding in the right direction so the learner realises the answer himself c) saying "shut up, you are stupid" or "go away, I am busy". The lad asked for help so he should be given it. We all start somewhere and we never...
  5. SgtTrojan

    Equipotential Bonding dilemma

    Agreed ^^ 1. Main protective bonding (single 10mm²) to the point of entry where the suppliers and consumers' installations meet. As there is no stop cock make the connection 600mm from the floor. This will ensure any changes made by the Water Authority will not affect your equipotential zone...
  6. SgtTrojan

    Neutral and earth bar in a consumer unit

    I totally disagree with this reply. This forum would be the first place I would come to to ask for clarification on anything. We have experts with more or less instant opinions or facts with knowledge of all the statutory and non-statutory documents available. Let's not lose the intention or...
  7. SgtTrojan

    Can you use a RCD as a Isolater in the c/u

    Does the installation have an earth electrode?
  8. SgtTrojan

    Cost of Periodic Inspection Report

    £120-£150 But if you buy me a drink I'm anyones :P
  9. SgtTrojan

    Is this going to be costly?

    A very conscientious fridge man if you ask me :shock:
  10. SgtTrojan

    Can I charge for small electrical jobs?

    :D :D :D I only think about you Sheds :D
  11. SgtTrojan

    Can I charge for small electrical jobs?

    I love that quote. Then I really do have a vivid imagination but a very apt image I think? :D
  12. SgtTrojan

    Can I charge for small electrical jobs?

    LMAO is it just me or does anyone else imagine this as a judge back scuttling the said party over the dock? LMAO :D :D :D :D :D
  13. SgtTrojan

    Cross Bonding of main bonding gas and water on PIR

    The Snags and Solutions book (Apr 2005) makes reference to 528-02-04 which is now given under 528.3.3 and states "Where an electrical service is to be installed in proximity to one or more non-electrical services it shall be so arranged that any foreseeable operation carried out on other...
  14. SgtTrojan

    Cross Bonding of main bonding gas and water on PIR

    This is not a recognised fault on one of the inspection boards and if a candidate insisted that was a fault and refused to seek further into that area of that board he would be failed for not identifying one of the twelve specified by C&G as pass criteria. The recommendation comes from the...
  15. SgtTrojan

    PIR Code

    :D edit: Sorry, i corrected my typo
  16. SgtTrojan

    PIR Code

    Proximity of Wiring Systems to other services - Section 528 "......neither a voltage band I or a voltage band II circuit shall be contained in the same wiring system as the same wiring system as the circuit of nominal voltage exceeding that of the low voltage" The 12 volt cable (band I) is...
  17. SgtTrojan

    PIR Code

    DOUBLE POSTINGS
  18. SgtTrojan

    PIR Code

    Or a 4 Prevention of detrimental mutual influence. Mixing Band 1 and 2 circuits. "Extra Low Voltage circuits should not be run in the same wiring system as 230v circuits unless all ELV cables and conductors are insulated for 230v or separated by an earthed metal screen. Reg:528.1"...
  19. SgtTrojan

    230v CONSTRUCTION site supply

    Yes. The three phase breaker used as a "loop"'for the other site supplies. The busbar is modified to allow for a single line connection. The earth is not connected. The neutral is brown. It was also a normal thing to see whereby the three radials all connected into one 32A cb. I can't...
  20. SgtTrojan

    230v CONSTRUCTION site supply

    Yes. The earth is twisted around the supply cable. Anything else? :D