  1. P

    Sunvic Actuator playing up

    Word of warning. They also always fail because everybody and I mean everybody always tightens the screws fully that hold them on to the top of the valve. Tighten them then back em off half a turn. Stan
  2. P

    Honeywell ST699B Battery

    Ohh might put mine on ebay then! Must be worth a fortune :P Stan
  3. P

    Worcester 28 cdi

    There is a small black square plastic adjustment on the D/Valve. Its a pig to get to and you need a 7 or 8 mm spanner. Its basically like a paddle so only a quater turn will turn down then back up to full. That is unless your inlet water supply is poo. Whats your cold tap like. Stan
  4. P

    Honeywell ST699B Battery

    You can get the original battery as a replacement for these. I have one on the van. Mind you have had it for a few years. Maybe you cant now? Will get the part number for you Stan
  5. P

    cooked P.C.B. , Ideal ISAR HE 30

    You could try replacing it with the new Esprit :P Same crock of poo, just more space inside to get in when you have to fix it :!: Stan
  6. P

    cooked P.C.B. , Ideal ISAR HE 30

    If the fans gone it will have popped the board. If you replace the board only the fan will pop it again. Make sure you replace both :!: Stan
  7. P

    Suitable replacement for Landis & Gyr MA-322 3 port valv

    Just about any 3 port mid position valve will be fine. Honeywell are usually the best in my opinion Stan
  8. P

    Myson Apollo 50B Boiler - Problems?

    The Pump overrun will not cause the boiler to cycle on and off. The only reason for whats happening if the boiler is working OK on Hot water is the 3 way valve. If the wiring is wrong or the valve is stuffed it will bounce in mid position giving you just the syptom you describe. I suggest...
  9. P

    Myson Apollo 50B Boiler - Problems?

    3 way valve is knackered and yes they are supposed to be wired that way. Stan
  10. P

    Worcester 24CDiOF burner lockout

    Make sure ignition pressure is correct or slightly higher than it should be. Stan
  11. P

    Radiator in a conservatory - Is my surveyor correct?

    I agree. I am a Logic certified trainer for Energy efficiency (part L) and my understanding is that you cannot put a radiator in a conservatory as the heat loss would mean the rad would have to be massive. You are allowed invertor Aircon(heat) or electric heating either underfloor or radiators...
  12. P

    ideal isar -lights with a bang!

    Ideal do not make an LPG Isar. Or should that be did not :? Stan
  13. P

    Vaillant ecoMAX 824/2 E

    Word of advice, at that age make sure that it isnt leaking down the back of the Heat ex from the condensate collector! The plastic collector was altered to sit into the heat exhanger around that time. Everyone always thinks its coming from the nut underneath. You will need the collector and...
  14. P

    Honeywell CM zone system

    What a suprise that you have this train of thought regarding new boilers when you are running one aswell!
  15. P

    Honeywell CM zone system

    If I was you I would stop ****ing money up the wall with this whole heap of rubbish and invest the money you are trying to waste making it controlable and efficient on a decent system and boiler which is controlable and efficient! 40 pence of every pound you are burning is being wasted at least!
  16. P

    potterton profile

    If I was you I would check the polarity at the power supply to the boiler :idea: and then kick yourself for wasting £140 on a new board. Stan
  17. P

    Worcester 280 Combi-Boiler not heating top floor

    You may also need to ensure that the expansion vessel is charged and charged to about 15 psi. If the expansion vessel is flat or low then a standard high head pump will only pump vertically 6 metres. It requires the artificial head created by the expansion vessel to get it up that high. Im...
  18. P

    Vokera 20/80 flowmatic fault?

    Try looking in the direction of the pump flow switch (bottom, back lefthand side). From memory, which is fading! the only usual course of no low speed fan is a stuck pump flow switch. Then again it could be the PCB or any number of other things on a boiler this age. Stan
  19. P

    greenstar 30cdi stuck in purge mode?

    Tony I never suggested he did! I mearly pasted on my experience that I have had these boilers stuck in purge mode and its the PCB.