  1. Diggory

    Heat Loss - Pen & Paper Check

    Hi again everyone - I’ve had a good look at my sizing now. Alas, I simply do not have wall space for the larger DT30 rads. I can however (just about) accommodate the DT40 sized rads. If I understand correctly, that will give me a flow / return of 70degC / 50degC ? And I’d be just below the...
  2. Diggory

    Heat Loss - Pen & Paper Check

    Thx - I’ll have a read D
  3. Diggory

    Heat Loss - Pen & Paper Check

    Thanks - I don’t mind paying for an app I just couldn’t find one - please send me a link to the one you are referring to Thanks D
  4. Diggory

    Heat Loss - Pen & Paper Check

    Thank you @endecotp - that’s a very valid point. I don’t think my boiler is sophisticated enough to have weather compensation. I guess my only option would be to manually adjust flow temp in summer months. I can 100% see the merit in the recommended DT30. What I’m grappling with is the...
  5. Diggory

    Heat Loss - Pen & Paper Check

    Firstly, thank you for advice and your generosity of time; it’s very much appreciated. There’s still lots I don’t know but I’m much better informed now, than when I started. To recap - - I didn’t get on with on-line heat loss apps - I calculated manually heat loss by room using areas / U...
  6. Diggory

    Heat Loss - Pen & Paper Check

    I’m only altering / repairing an existing system ? Replacing the 40yr old rusty / sludge rads (and trying to get sizing correct). And the boiler and UFH has been installed by a ‘competent person’. The same person will be fitting / flushing / commissioning the rads. D
  7. Diggory

    Heat Loss - Pen & Paper Check

    Sorry, I missed that reply; then figured it out myself 15mins later If I didn’t go the DT30 route; is it just that I’m not taking the opportunity to improve efficiency. And if I size of the DT50 data, it will suffice albeit at perhaps 10% less efficiency. Thanks D
  8. Diggory

    Heat Loss - Pen & Paper Check

    Sorry typo (so 4,5682 4,582W for two but still 620W short of what I’d need).
  9. Diggory

    Heat Loss - Pen & Paper Check

    If I’m calculating correctly………. One of my rooms has two rads set against requirement of 2,668W. My plan was (reading off the DT50 75/65/20 degC Table) 2x 1,400W Type 22; 450(h) x 1,100(w) = 2,800W (I can’t go taller than 450mm). Factored for DT30; the I’d need the equivalent of 5,202W (reading...
  10. Diggory

    Heat Loss - Pen & Paper Check

    Thank you @endecotp…….. The STELRAD data I’m looking at qualifies the T50 with ‘(75/65/20 deg C)’ . So the T50 is the delta of room temp at 20 deg C to the rad temp 70 deg C (being the mean of 75/65 flow & return). if I understand correctly - there is an opportunity here to make the boiler...
  11. Diggory

    Heat Loss - Pen & Paper Check

    Thank you @Notch7 and @Mister Banks for reply. The boiler has (just) been replaced; ecoFIT pure 825 combi; 25 kW / 85,000 BTU. (Old boiler was Potterton 60e 18Kw). New boiler plumbed with two zones: - Z1 17sqm UFH installed and running now. - Z2 x9 rads; flow/return not yet connected -...
  12. Diggory

    Heat Loss - Pen & Paper Check

    Thanks to advice gratefully received, I’ve generated my radiator shopping list (from U values / areas etc and no Apps). I wanted to check against rads that came out (sensible advice from @oldbuffer) that I’m in the right ball-park. I get the feeling the new rads are a tad larger capacity wise...
  13. Diggory

    Towel Rail / Duel Fuel / Heat-miser

    I’m in process of moving from vented to combi…… I’d like to put a new towel rail in the airing cupboard where the old HW cylinder was removed from. I’m pondering a low wattage electric element for when the boiler is on summer holiday. The alternative (grateful of thoughts); I have a...
  14. Diggory

    Heat Loss - Pen & Paper Check

    Thanks reply. I was concerned that because it has a high thermal mass (big lump masonry), I would need to assume something like a 10 or even 21 deg temp differential. D
  15. Diggory

    Heat Loss - Pen & Paper Check

    I’m working through my rooms; one by one. The internal wall of two rooms is largely made up of fireplace / double chimney breast. I’ve peered in from loft - it’s a single course of bricks with about 300mm of ‘in fill’ in the void between chimney. Would someone be kind enough to suggest a U...
  16. Diggory

    Heat Loss - Pen & Paper Check

    Thank you for the advice…. - I’ve added a 10% weighting for intermittent heating - I’ve assigned different temperatures based on room type - I’ve included heat losses to adjacent internal rooms - I’ve identified solid / cavity walls (from advice on brick bonds) - I’ve dialled back the U value...
  17. Diggory

    Heat Loss - Pen & Paper Check

    Thank you @endecotp - that’s an interesting idea. D
  18. Diggory

    Heat Loss - Pen & Paper Check

    240mm measured at a Window. D
  19. Diggory

    Heat Loss - Pen & Paper Check

    I’ve had a look at my brick bond on older (200mm) walls of house. The oldest part follows the bond pattern you describe: It then transitions to a newer (still old) bond of 2x long bricks followed by a half brick - would this be solid too ? Thanks D
  20. Diggory

    Heat Loss - Pen & Paper Check

    Thank you @oldbuffer - that’s very helpful and generous of your time. As you suggested…… - I’ll add +10% for intermittent heating. - I’ll dial back the U value on the 1957 walls too. - I’ll have a look at the ‘brick bond’ on the older walls to see if I can get a better read out on the...