  1. M

    Excessive Gas Consumption - Not sure what to try next!

    Where does Tado get its information from?
  2. M

    Excessive Gas Consumption - Not sure what to try next!

    I live in a large 4 bed house built in 1996 in the south of England and our gas usage for December was just over 1900kWh so I think you have an issue at 5000kWh usage. From what you have said there is no gas usage when the boiler is off so there must be an issue with the boiler setup.
  3. M

    Loft legs or new timber frame

    I went with Loftzone because the system is a lot lighter than using timber and more stable than using loft legs alone. Timber adds a lot of extra weight to the loft floor.
  4. M

    Does anyone make a thermostatic radiator valve with a timer?

    It depends on the heat loss of the rooms and how low the boiler will modulate down too.
  5. M

    Does anyone make a thermostatic radiator valve with a timer?

    If too many radiators are off the boiler will short cycle likely resulting in higher energy usage than just leaving the radiators on.
  6. M

    Boss Therm (Siemens) BR1 + Boiler. Trouble with CH coming on

    Have you manually opened the CH zone valve? If so that is why you now get CH heat when the HW demands it.
  7. M

    Help with wiring in a new Hive thermostat

    You said you disconnected the old thermostat wiring from the honeywell wiring centre, the terminals you disconnected the wires from will need to be connected together.
  8. M

    Help with wiring in a new Hive thermostat

    You can not just disconnect the thermostat as you will leave the heating open circuit. In the wiring centre loop the 2 connections together where the thermostat wires were terminated.
  9. M

    Loft legs or new timber frame

    I used loftzone...
  10. M

    How to wire Nest to both a boiler and a second pump

    That sounds odd to me. If the towel rail is on the secondary return then it will only heat up when a hot tap is turned on. As you say off topic so enough said.
  11. M

    How to wire Nest to both a boiler and a second pump

    I know that. :) Why would you have a radiator/towel rail on the HW circuit?
  12. M

    How to wire Nest to both a boiler and a second pump

    But the towel rails cant be coming on with the DHW circuit, they will only come on when a HW tap is opened. If they were on the DHW circuit they would have inhibitor.
  13. M

    Blocked radiators - Fix or replace? Help needed!

    Are the rooms heating to the required temperatures? If so I don’t think you have a problem based on the thermal images.
  14. M

    Radiator under window sill

    How would it look if you screwed a couple of wooden battens to the wall for the brackets to attach to, would that be sufficient for the top of the radiator to then clear the sill?
  15. M

    Radiator under window sill

    Radiators should be installed with 150mm between bottom of radiator and the floor in order to maximise the convection capability.
  16. M

    Updating Controls

    Wiser room thermostats only adjust room temperature. Timer control for HW and CH is all done via an app. I believe Tado is the same.
  17. M

    Updating Controls

    Sorry, finger trouble ignore the word "other".
  18. M

    Updating Controls

    Wiser and, I think, Tado aren’t combined thermostat/programmers. The other room thermostats are just that and the programming is done via an app. Wiser still functions with no internet but Tado doesn’t.
  19. M

    Cold rooms in the back of the house

    The picture doesn’t look like it’s the lockshield valve, the LS will be on the other end of the radiator and can only be turned with a wrench.
  20. M

    Wiring up combi for s-plan

    That’s good but it is costing you more in energy which is the opposite to what most people want.