  1. R

    underfloor heating only works in some rooms

    Hi all, have a wet underfloor heating system. the issue i have is that some rooms/loops work fine and others the floor stays stone cold. new pump was fitted and the supply is hot so no issues there. blending valve set to 45/50 and the flows all read about 2ltrs. the returns come back luke...
  2. R

    purging underfloor heating

    also, what pressure should the system be on?
  3. R

    purging underfloor heating

    my manifold is below all the floors...
  4. R

    purging underfloor heating

    well I can close one end of the loop as it were , but wont it continue draining into the manifold etc?
  5. R

    purging underfloor heating

    HI ALL. last ditch attempt to get my UFH working in some rooms,some are fine. I want to purge the system of air which im fine to attempt. my problem is that I can close both ends of the individual loops . I have the balancing valves at one end of each loop where I can screw them down to stop the...
  6. R

    Underfloor heating problem

    No carpets its wood floor
  7. R

    Underfloor heating problem

    cheers, i'll go and hire a power flusher etc
  8. R

    Underfloor heating problem

    Yes ,I've had it running for most of a day and still nothing.
  9. R

    Underfloor heating problem

    sorry to double post, but if there is some crud blocking it, and cleaning fluid helps budge it, could the dirt/ whatever block somewhere else?
  10. R

    Underfloor heating problem

    so I just introduce the cleaner thru the manifold filling point? or how do I put it through? I guess the same with the inhibitor?
  11. R

    Underfloor heating problem

    what product do u think I could try to introduce my self? is it ok to leave it in the system for that long etc?
  12. R

    Underfloor heating problem

    good point.. perhaps I'll just bite the bullet and get someone ELSE in! thanks for all your help and advice buddy
  13. R

    Underfloor heating problem

    when I feel the floor by hand it feel stone cold. is the power flush something I can do my self , or do I need some sort of pump etc? when I purged the loop the water coming out was clear...
  14. R

    Underfloor heating problem

    the thermometer on the flow shoe anything from 50-60 degress. when I have the mixer valve set to say 45 the temp guage on the return shows 30 ish at say 2 ltr /min. I know the difference should be about 8-10 degrees . the last plumber said he thinks by looking at the water in the flow gauges...
  15. R

    Underfloor heating problem

    yes the flow pipe to the "cold" room is very hot, the return comes back luke warm , does get a bit hotter when I turn the mixing valve up or the crank the flow right up.. screed I believe. haven't tried to touch trace the heat.i guess I can try that later. the way the floor and pipes are layed...
  16. R

    Underfloor heating problem

    What problems can the manifold have? Not actuator as I have taken them off and let the system run ..
  17. R

    Underfloor heating problem

    Hi. They have worked before. How would I know if there's a blockage? When I purged that loop the flow showed 4 ltr/m . How do I know if there is some bypass as mentioned above? Room still cold even if only one on
  18. R

    Underfloor heating problem

    Morning. Yes they have worked previously. As we're fine when my 1 kid slep there.
  19. R

    Underfloor heating problem

    all the actuators are controlling the right rooms..if that's what you mean?