  1. Riki

    Switch wire. 2 of 3 are live!

    Tested between the reds and the switched live wire with the wall switch ON. I know I don't fully understand but I am trying to the best of my ability.
  2. Riki

    Switch wire. 2 of 3 are live!

    My measurement is from the reds to the switched live wire with the wall switch ON. Here is the photo.
  3. Riki

    Switch wire. 2 of 3 are live!

    Latest. A voltage test in Room 2 shows only 35 volts on the multimeter. In Room 1 248 volts.
  4. Riki

    Switch wire. 2 of 3 are live!

    Of course I got that the other way round! Old age creeping in...
  5. Riki

    Switch wire. 2 of 3 are live!

    The photo in #28 is no longer valid. I changed the wiring: brown to switched live and blue to neutral.
  6. Riki

    Switch wire. 2 of 3 are live!

    Brown is live and blue neutral. Changed from red live and black neutral, green of course is earth.
  7. Riki

    Switch wire. 2 of 3 are live!

    Yes but aren't the brown/blue interchangeable?
  8. Riki

    Switch wire. 2 of 3 are live!

    Second: switched live wire Third: 2 black neutrals
  9. Riki

    Green goo

    Thanks for your comments flameport. I'll bear in mind what you have just told me.
  10. Riki

    Green goo

    Has anybody out there experienced the, I believe, traumatic experience of a full house rewire caused by the appearance of green goo? Over the years I have cleaned some sockets contaminated with the green stuff. Should I consider a rewire even if only some sockets and one or two switches are...
  11. Riki

    Switch wire. 2 of 3 are live!

    1. Bulb OK. Tried with other bulbs just in case. 2. No loose wires, all checked. Rose and switches. 3. Lamp 2 rewiring is correct: 3 reds, 1 switched live, 2 neutral and 3 earth. Continuity OK. 4. Re metal sticking out on a red wire is because the insulation is short. Was like that before I...
  12. Riki

    Switch wire. 2 of 3 are live!

    Still no luck after checking all switches (with multimeter). All I am getting is a flickering light (when I touch the bulb) in Room 2 and not even that on the other lights affected, all dead. Room 1 still OK together with entrance lights, lounge/dining and kitchen. 8 lights working, 10 not. No...
  13. Riki

    Switch wire. 2 of 3 are live!

    We've had goo in some sockets over the years that have been cleaned. Emptying the house for a rewire is not something we will consider unless absolutely necessary.
  14. Riki

    Switch wire. 2 of 3 are live!

    Had a closer look and discovered that the black wire in the switch was covered with green gunge; cleaned with meths, cut and stripped fresh end and now I am getting the switched live black wire on the rose. Will wire again tomorrow, time for dinner. Watch this space! Hope it works this time.
  15. Riki

    Switch wire. 2 of 3 are live!

    Checked the switch. No joy. No continuity in OFF but continuity in ON.
  16. Riki

    Switch wire. 2 of 3 are live!

    Perhaps, but I am not giving up just yet.
  17. Riki

    Switch wire. 2 of 3 are live!

    Good point. I'll check the switch. Checked the switch. No joy. No continuity in OFF but continuity in ON.
  18. Riki

    Switch wire. 2 of 3 are live!

    This is the result of the test: (circuit de-energized and switches on) in Room 1 the connections are correct, the red wires and the switched live wire have continuity (beep). However, in Room 2 none of the 3 black wires have continuity with the reds, i.e. no switched live wire. What next? What...
  19. Riki

    Switch wire. 2 of 3 are live!

    Thanks, I'll come back.
  20. Riki

    Switch wire. 2 of 3 are live!

    Thanks, I'll come back.