    Gas boiler overheats on valve closure - vented system

    A Y plan could work. Why would this not have been done in the first place? Excuse my ignorance but can a Y plan heat both immersion and rads at same time?
  2. P

    Gas boiler overheats on valve closure - vented system

    Confirmed - the boiler running the pump but not firing. T
  3. P

    Gas boiler overheats on valve closure - vented system

    The bypass is adjacent to the pump in the airing cupboard 5 metres away (ten metre flow & return). It would be tricky to fit a rad. This should be unnecessary as the boiler did not overheat before the bypass valve was fitted when there was a gate valve that was partially open. The auto...
  4. P

    Gas boiler overheats on valve closure - vented system

    Both valves closed it still runs. If hot water cylinder demand met, then heating demand met, both valves close and pump continues to run on a cooling circulation I guess determined by the boiler. I'm pretty sure the pump is wired to the boiler.
  5. P

    Gas boiler overheats on valve closure - vented system

    Unfortunately each time it boils its probably creating air in the system.
  6. P

    Gas boiler overheats on valve closure - vented system

    It'd be easy enough to drain from the boiler see what comes out. The boiler is downstairs, the pump & bypass are in the airing cupboard are upstairs. Sediment could be sitting in the boiler.
  7. P

    Gas boiler overheats on valve closure - vented system

    I need some ideas on diagnosis of an overheating boiler in a conventional vented central heating system. The system has two valves controlling heat circulation through radiators and a water cylinder respectively. When either of these two valves closes, without the other valve being open...
  8. P

    Extractor fan triggered by shower pump

    Thanks for the advice - I'll be having a look at the options over the next few days and discussing with the electrician. I like the look of the Iconfan and can see that installation will be very simple - as long as it runs quiet! Cheers
  9. P

    Extractor fan triggered by shower pump

    Thanks for the responses! Preference is to not have any noise - I can't stand the sound of a extractor fans. Whilst in the shower there's plenty of ambient noise - in the bath... Maybe my experience of extractor fans are bad ones - are there almost silent runs available? I have option...
  10. P

    Extractor fan triggered by shower pump

    Thank you for the advice. A flow switch would work and be ideal and an overide switch could be in circuit for a non-shower user to use the fan. A humidistat would work but as you suggest I would want to be able to isolate it when taking a bath.
  11. P

    Extractor fan triggered by shower pump

    I'm looking for an extractor fan for bathroom/shower room. Ideally I'd like it to operate only when the shower pump operates with a timer to overun. Does anyone know of a product that will connect in this way? Thanks
  12. P

    Mira 88 shower control - Removal without damaging tiling

    Thanks for the offer Allan but I've already got a kit.
  13. P

    Mira 88 shower control - Removal without damaging tiling

    Had a look at the Combiforce - fell off my stool - lot of money £224. Control came off a treat this morning albeit with a big hole in the wall. Stripped it on the bench - this thing is built so well I'm not going to scrap it. I'll buy some new plastic trims and fit the service kit then...
  14. P

    Mira 88 shower control - Removal without damaging tiling

    Thanks - I'll shall remove the assembly tomorrow. Hopefully it'll be serviceable and can go back on. Suspect I maybe better off fitting a new shower control. Any recommendations on a make that will have a similar footprint to cover the holes left by the Mira?
  15. P

    Mira 88 - Fit service kit

    Its the one with the square type unions. I'll have a go tomorrow. Thank you for the advice!
  16. P

    Mira 88 shower control - Removal without damaging tiling

    Thanks for the reply BingoBongo Its exposed type. To confirm - its the allen key accessible from under the valve body and the two 15mms nuts are the ones going into the tiled wall?
  17. P

    Mira 88 shower control - Removal without damaging tiling

    Anyone tell me how to remove a Mira 88 please. I don't want to crack the surrounding tiles.
  18. P

    Please ignore - duplicated post

    Please ignore - duplicated post
  19. P

    Mira 88 - Fit service kit

    I have a Mira88 with a leak from the centre spindle. Based on experience with another property I went ahead and bought a service kit and new knobs. Trouble is this one hasn't been apart like the last one which was only a couple of years old. This one I can't rotate the big nutted cover...
  20. P

    Shower Pump choice

    The Monsoon's been in the loft a year and is doing really well for a secondhand unit. Its as quiet as it was and really is unobtrussive - not as loud as vacuum cleaner. All I did as a precaution was to mount it on the slab - an acoustic box was unnecessary. Only thing an issue is the way...
Back
Top