    I have discovered I have a Myson 2 Port power extra MPE222 head for a 22mm valve/pipe, fitted to 28mm valve/ pipe. There is a MPE228 available obviously for the 28mm pipe. The 28mm version is a 5 wire head (has a white wire in addition) whereas the 22mm has 4 wires (no white) I have the...
  2. R

    RCD keeps tripping

    Terry your a diamond, cheers
  3. R

    RCD keeps tripping

    Terry, Removed the brown wire from T2 and the result= no tripping of the main power RCD, so that sounds encouraging, can you please advise cheers Ian. As you were probably aware this brown wire is part of the loom connecting the other M/V (CH) I guess so I am assuming this points towards a fault...
  4. R

    RCD keeps tripping

    Thanks I will give that a try tomorrow.
  5. R

    RCD keeps tripping

    Thanks just to confirm the brown wire in terminal 2 ?
  6. R

    RCD keeps tripping

    Cheers for the reply. You are spot on sir the G/Y wire connected to the brown wire terminal 8 goes to a terminal underneath the temp gauge fixed to the side of the mega flow tank. The GY has a red (live ) sleeve on one end but not on the end in terminal 8. I was beginning to doubt myself with...
  7. R

    RCD keeps tripping

    Thanks for getting back to me I understand what you are saying I must have made a mistake rewiring the MV, unfortunately I have no reference point to know where the earth wire in '8' would go I took a picture with my camera prior to removing the wires so I am baffled, you obviously can't tell me...
  8. R

    RCD keeps tripping

    Thanks for all your help appreciated. I have 2x two port motorised valves, the one I have had problems with preventing the boiler from firing up with demand for hot water, HW motorised valve and the other a myson with a white cover will be for the CH system I assume. So could it be either MV...
  9. R

    RCD keeps tripping

    Cheers for the assistance, Hopefully pictures may clarify and I take your point, I haven't used the CH after re fitting the MV apart from yesterday when my wife tried to put the heating on tripped the RCD straight away, when I tried it 2 mins later CH worked and I bled out all the rads reached...
  10. WP_20170914_002

    WP_20170914_002

    Wiring Box lid
  11. WP_20170722_001

    WP_20170722_001

    Wiring box HW CH
  12. WP_20170914_001

    WP_20170914_001

    Holywell room stat
  13. R

    RCD keeps tripping

    Thanks for that, I have just checked again, turned the programmer on to CH 'on' left it for 5 mins all ok, as soon as I turn the room stat for heat it trips the RCD. I will try a new room stat although I only replaced the old Hollywell one about 18 months ago.
  14. R

    RCD keeps tripping

    I was hoping it may be a faulty programmer I have the British Gas UP2 programmer , just found a second hand one on flee bay, if its a like for like replacement would it just be take the old one off the backpkate and push fit the new one ? Actually just found a Drayton LP722 programmer...
  15. R

    RCD keeps tripping

    Appreciate the replies, my electrical knowledge is very basic so I wouldnt feel competent to carry out those checks. Not sure about the forum rules are you allowed to offer your sefvices on here ? I live in Weston Super Mare
  16. R

    RCD keeps tripping

    Thanks for replying appreciate that , it is fine with the HW supplies everything as it should
  17. R

    RCD keeps tripping

    Hello, RCD is tripping when I move the room stat to (call for heat). Conventional boiler, Mega Flow system, was having intermittent fault with the motorised valve where the boiler wasn't flashing up to supply hot water, removed the MV a few weeks ago fitted a new one and wired it in only to find...