mate suffered this every time neighbour used tap fitted simple shock arrestor straight after stop cock and it solved it
https://www.screwfix.com/p/flomasta-vessel-shock-arrestor-1-1-2-bsp/905fa
you wont cause a leak just break the bits off as none of the box forms any sort of seal with the gas service .
The black ring is possibly just like a big circlip holding pipe to box
Then you need a mark2 surface box when replacing it...
cylinder stat is also placed far too high on the cylinder and temp is low at 50
Filter on expansion pipe ?
Not the clearest of photos but it looks like your pump is on the flow into cylinder
No solution to your problem but in the hundreds of plates i have had out changed/cleaned etc i have never seen anything that resembles how gritty that looks . In one side of the plate let along both sides . Very strange
there is an auto vent on top of the pump usually screwed down
Noise on the instants on pre heat was usually a whistling sound associated with the divertor valve
not strictly true failure of the gas valve / thermostats and other components can keep a boiler on in fault condition causing the pressure to rise as expansion vessel cannot accommodate the amount of expansion from the heat being generated
which can be dealt with with chemical clean and hot and cold flushes in the vast majority of cases . But then again that doesnt generate £££ for unnecessary work
yep the biggest boiler manufacturer in UK needs to take advice from JOHND and older plumbers need to stop adhering to manufacturers instructions on how to fit their boilers despite this voiding warranties.
.
oh look here is ideal also saying the same .
.
.