  1. O

    16mm joint

    Hi, I need to change an old rusted switch fuse on my property but the cable in side will be about half a m short or less... I have a crimper and some 16mm through crimps (uninsulated) but just wanted to know how to make it safe in the enclosure? Wrap each crimp in insulation tape then heat...
  2. O

    Long Long Cable Run

    Thank you so much for your help.
  3. O

    Long Long Cable Run

    Thanks for your reply. I have seen pictures of the units we are to hire and had specs... they are connected via a 240v 32a plug to the electric supply and there are lights, water pumps for showers etc and for waste. There are also what looks like water heaters above the sinks powered by fused...
  4. O

    Long Long Cable Run

    so what is the max current with the existing cable I can use?
  5. O

    Long Long Cable Run

    our supply voltage is between 242-247v and we also have access to 3 phase. What are my options? Im having an even soon and we are hiring some toilets and showers (showers are gas powered) but both these need a 32A supply. When using the tool at the TLC site it says the cable is good for 50A...
  6. O

    Long Long Cable Run

    its printed on the cable.... when you say wrong what do you mean?
  7. O

    Long Long Cable Run

    16mm twin and earth in 4inch ducting from house to control panel (40m) then 16mm 2 core SWA from control panel to out building (40m or so )
  8. O

    Long Long Cable Run

    Hi, Just moved in to a new house that has a large out building about 80m away from the house. I was told by the last owner that the supply was good for about 63a in the out building but after closer inspection I now doubt that! There is a 16mm cable coming from the house via a 63a MCB then...