  1. W

    Shower not on RCD

    Good point. I won't proceed unless there is an isolator between the meter and the CU. I would be surprised if there is not one as the DNO had to move the incoming cable, cutout and meter when the extension was built.
  2. W

    Shower not on RCD

    Is this any clearer?
  3. W

    Shower not on RCD

    Hi, Here is a new picture I took this afternoon: The shower circuit is the leftmost, next to the main isolator. Is this 6mm2 cable? I note that for the two circuits that the spark installed, he has not even gone to the trouble of shrouding the CPC. I guess he also replaced the...
  4. W

    Shower not on RCD

    Thank you guys :D You have all gone to a lot of trouble to help me understand the reasons why an RCD is desirable in this situation and I really appreciate it – that’s what I wanted, a better understanding. Fitting another enclosure would be tricky due to space constraints where the CU is...
  5. W

    Shower not on RCD

    Not meaning to be pedantic here – just trying to increase my understanding and I’m grateful for the input so far. I don’t understand your distinction between points 1 & 2. Point 1 – I think I understand – you come into contact with live and provide a more attractive path to neutral via the...
  6. W

    Shower not on RCD

    Great link - thanks. That was a really good scenario (worn seal) Now I can't understand why RCDs for showers are not mandatory :shock:
  7. W

    Shower not on RCD

    This is where I am a little fuzzy. My hobby is electronics so I have a good basic understanding theory wise but I’m trying to work out a scenario where it would be dangerous. I know an RCD looks for balance between phase and neutral and is therefore very sensitive to small current leakages. A...
  8. W

    Shower not on RCD

    Wow - quick replies. Unfortunately I did use a phone and there’s no flash on it. I could only see how crap the pictures where when I got home. I will take my proper digi camera over tomorrow and get some decent photos. There an isolation ceiling pullswitch next to the shower. It’s a...
  9. W

    Shower not on RCD

    Hi, I’ve been reading through these forums and I’m hoping that some of the regulars can give me some advice please – and I know that you love pictures, so I’ve included some! I took these photos with my phone but I can take my digi cam over there tomorrow and take some more if these are not...