  1. H

    Dead boiler Vailant Ecotec Pro 28

    yeah very odd. Thanks for all your help. Really appreciated.
  2. H

    Dead boiler Vailant Ecotec Pro 28

    Wolseley had one in stock nearby so I shot over there before 5 and picked it up.
  3. H

    Dead boiler Vailant Ecotec Pro 28

    I replaced the pcb with a new one and it’s fired back up!
  4. H

    Dead boiler Vailant Ecotec Pro 28

    Cant get an engineer here for a week at the earliest
  5. H

    Dead boiler Vailant Ecotec Pro 28

    Checked pump with meter and there is 240v there when heating sequence starts. That’s what’s running for 10 secs before boiler shuts down. Don’t think it’s the pump. As before. As soon as hot tap is on boiler shuts down
  6. H

    Dead boiler Vailant Ecotec Pro 28

    can here a low hum not sure if it’s the pump Gave the pressure sensor a jiggle And checked the plug on the end s.97 gone but same prob shutting down
  7. H

    Dead boiler Vailant Ecotec Pro 28

    S.30 in when boiler on standby the S.97 when applying heating looking online it says S.97 Water pressure sensor check is running, demand (DHW or heating) is blocked
  8. H

    Dead boiler Vailant Ecotec Pro 28

    If I fit the link wire between 24 & RT something starts to run for about ten seconds but it’s not the boiler firing. But then then the boiler shuts down
  9. H

    Dead boiler Vailant Ecotec Pro 28

    the 24v ones. Via the hive control unit.
  10. H

    Dead boiler Vailant Ecotec Pro 28

    The boiler has both 24v & 230v RT connections.
  11. H

    Dead boiler Vailant Ecotec Pro 28

    Definitely getting 24v between neutral & RT terminal not 240v sorry flash may have been incorrect. Poss. The resettable fuses .
  12. H

    Dead boiler Vailant Ecotec Pro 28

    Even with hive disconnected at the boiler and boiler reset it still has a S.30 code when using the buttons to view
  13. H

    Dead boiler Vailant Ecotec Pro 28

    Bridge removed. Tested voltage at Neutral and the RT terminal 4. 24v present. nothing at the 24v terminal 3 & neutral
  14. H

    Dead boiler Vailant Ecotec Pro 28

    If I bridge 3 & 4 the pre heat starts then boiler shuts down. Getting a flash of light off the pcb too I noticed
  15. H

    Dead boiler Vailant Ecotec Pro 28

    i bypassed the hive by fitting the link wire back in the boiler. Same problem
  16. H

    Dead boiler Vailant Ecotec Pro 28

    S.30 code Room thermostat is blocking heating mode I have a Hive wireless stat connected to the boiler
  17. H

    Dead boiler Vailant Ecotec Pro 28

    yeah re-connected after testing it.