This is, in reality, is NOT the minimum flowrate required, most, if not all, publish a flowrate simply based on a boiler flow/return dT of 20C,
So a 18kW boiler will require a flowrate of , 18*860/60/20, 12.9LPM. A 24kW boiler will require, 24*860/60/20, 17.2LPM, etc. If the minimum output of...