    Downstairs heating only working when upstairs is on

    LOL - I should have used Waygo’s as got loads in the shed
  2. R

    Downstairs heating only working when upstairs is on

    Yeah I did intend doing that but there were so many wires in the terminals I had to remove some to get the new ones in - I was rushing it as well. School boy error for sure but grateful for the help on here
  3. R

    Downstairs heating only working when upstairs is on

    Hi all - the issue is all resolved, it was all my fault as I had wired the new valve head incorrectly (put the grey into the same as the orange) - thanks very much for all your help,
  4. R

    Downstairs heating only working when upstairs is on

    Should there be one grey in the terminal with the oranges (not a grey from the valves) that sends the live to the boiler?
  5. R

    Downstairs heating only working when upstairs is on

    It’s a new problem - it started with downstairs stat not turning on the boiler but fault seemed intermittent at first but then it wouldn’t tum boiler on at all but it all works perfect when upstairs is on. I replaced the downstairs stat and the valve head but problem persists.
  6. R

    Downstairs heating only working when upstairs is on

    I am starting to think I may have got one of the grey wires mixed up between terminals 5 and 6 - do the grey wires from the valve head get connected in the same terminal as the orange?? This could be my issue as at the moment the grey wire from the new downstairs valve head is connected with the...
  7. R

    Downstairs heating only working when upstairs is on

    This is the stat (I had taken the earth sleeve off) - am getting 240 on the brown and 240 back in the main control box when switched on
  8. R

    Downstairs heating only working when upstairs is on

    I am getting 240 on terminal 8 when the downstairs thermostat is turned on (and 240 on terminal 9 when upstairs stat is turned on) so I assume that rules out the wiring from the thermostat. Sounds like it can only really be a bad valve head switch or could it a bad valve that’s not opening...
  9. R

    Downstairs heating only working when upstairs is on

    Merry Xmas everyone By way of an Update - have tested as per the advice above and I only get 240v when the upstairs is on. Could it be that h new Honeywell valve head I have installed is faulty or maybe it’s an issue with the thermostat wiring (but not sure how it can be as the thermostat is...
  10. R

    Downstairs heating only working when upstairs is on

    Will have a look but I did remove this and reconnect/check everything this morning and the downstairs still wouldn’t work (unless the upstairs/boiler was on) - am totally baffled
  11. R

    Downstairs heating only working when upstairs is on

    Thanks - that’s really really helpful - I am out for the rest of the day but will have another look tomorrow
  12. R

    Downstairs heating only working when upstairs is on

    This is the wiring box - not really sure what I am testing to be honest
  13. R

    Downstairs heating only working when upstairs is on

    Thanks but the downstairs does come on providing the upstairs is also on
  14. R

    Downstairs heating only working when upstairs is on

    Yes I have got a multi meter and enough knowledge not to kill myself. Have already wired in the brand new valve head earlier today which I had hoped would solve the problem
  15. R

    Downstairs heating only working when upstairs is on

    Thanks - so it’s getting power to the valve to open the valve but then not sending it on to the boiler. So do I need to check/follow/test the orange wire between the valve and the boiler for any issues?
  16. R

    Downstairs heating only working when upstairs is on

    No the downstairs don’t come on unless the thermostat is cranked up