Not a recommended setup but,:
https://www.jtmplumbing.co.uk/central-heating-controls-valves-c436/belimo-2-3-port-valves-1-2-to-2-c408/belimo-3-port-zone-valve-with-240v-actuator-powered-open-spring-close-p21843
there is a autore-set high limit thermostat. its in the manual.
check circulation? covers off may be helping as there's little insulation on these buckets.
to big for load?whats it heating
http://www.ebay.co.uk/itm/Thermal-Store-Hygienic-Buffer-Accumulator-Tank-for-biomass-boilers-wood-heating-/151748302522?pt=LH_DefaultDomain_3&var=&hash=item2354e756ba
i ordered a custom steel one. good quality and insulation is very well made. Arthur is the person i spoke to.
what was the co2% in the flue gas?
sounds as if its burning to lean. 300 is too hot.
Take a note of the air damper setting, then close it slightly.
a little bit at a time, to see if that improves ignition.
or use your fga to check co2 is 12%...
Primary store stat changed?
Hidden behind panel, try adjusting it down slightly with a small screw driver. It'll be painted in a fixed position.
expansion vessel fexi hose blocked?
Not long completed a similar job although boiler was moved into loft, so more like 30odd meters of extra copper. Decent boiler fitted though and lpg. 2.5 days. Wireless programmer retained. Job done to current standards.
little guy = 2400