    Socket too low but cable to short to move.

    The BS standard if I recall says 20A for 4 hours, but I was talking about what I was taught when I did electrical training long before Part P came in. What normally happens is people spur off spurs, effectively creating radial circuits. No one sticks to the rule of only a single socket (twin or...
  2. M

    Socket too low but cable to short to move.

    I was looking for some other advice and stumbled on this post, so sorry for bumping a 2 year old thread. I'm not sure that's good advice. If they use 2.5mm to spur from a ring, and connect a twin outlet at the end of the spur, then the cable won't be rated properly. It has a max of 24A, whereas...