Hi,
Boiler fires ok in h/w mode but refuses to fire in CH mode.
Thermostat looks ok - clicks when powered and moved above ambient temp. Also overriding thermostat (shorting the live to call) does not cause CH to fire.
I think that I have a faulty mid-position valve (ACL 679H340-30L0)...