Search results

  1. W

    Honeywell CM927, HR80UK not binding to HC60

    Dave I'll have to monitor the situation with the valve base, it seems to be working OK but I have been concentrating on the binding process so may not have noticed it. Wils
  2. W

    Honeywell CM927, HR80UK not binding to HC60

    Dave You are a star Just gone through what you said, didn't even know there was another boiler teach in mode, this was the vital piece of information missing from anything that I have seen, don't know where you got it from but thank you. This is how I set the system up for info, (if...
  3. W

    Honeywell CM927, HR80UK not binding to HC60

    Instruction manual for CM927 page 11 section 5.2 states that it is compatible with the HR80. I can get it to work as already described. Have you got one and thinking of getting the HR80'?
  4. W

    Honeywell CM927, HR80UK not binding to HC60

    Has anyone managed to get a CM927, HR80UK and a HC60 setup to work correctly, if so how. :cry: I can get the CM927 to send set points to the HR80UK, I can get the CM927 to switch the boiler on via the HC60 but I can't get the HR80UK to switch the boiler on when the CM927 is in a room with no...