  1. J

    Point of User Water Heater (Sadia)

    Cheers for the reply. So long as I know what's going on I won't waste any time trying to repair it!
  2. J

    Point of User Water Heater (Sadia)

    Hi, I have an ageing Sadia water heater in the kitchen which has recently started playing up. It drips constantly from the spout (more than expected from venting) until eventually after several hours the tank is virtually empty, at which point the element cuts out. If I open the inlet...
  3. J

    Replace Built In Electric Oven

    Thanks for the advice Chri5, much appreciated. From my calcs 3kW/230V = 13.04A. If I use a 20A MCB that leaves 7A available for the socket. Would this be enough for the ignition? (I don't have the spec for the hob off hand).
  4. J

    Replace Built In Electric Oven

    Thanks for the response. The model is Electrolux Intuition EOB 53000K. Yes, it is 6mm twin & earth and the cooker control unit is a standard cooker point with integrated 13A socket. The connected load (from Electrolux's site) is 3kW.
  5. J

    Replace Built In Electric Oven

    I have bought a new built in oven to replace my old one and I'd like to confirm a few things before I start. The old oven was wired directly to a cooker control unit, which has an additional 13A socket. This was hard wired to a 32A MCB on the consumer unit using 6mm flex. I want to replace...