Search results

  1. T

    Ideal Classic FF

    Thanks to both. I will try the drain suggestion first and then mess with the sparkies later if necessary! With all this draining, what do you advise as regards replenishing the inhibitor, and is this best done by adding to the header tank?
  2. T

    Ideal Classic FF

    ...and unfortunately we still have the problem!
  3. T

    Ideal Classic FF

    You're right to check and yes, there is water in the sytem and it replenishes.
  4. T

    Ideal Classic FF

    The pump continues to run when the boiler goes out, the boiler fan also runs (sorry to keep harping on about that). They both continue to run indefinately or until the room stat is manually tripped or the programmer is swithched off. The pump body is warm/ hot and the pipes are cold. There seems...
  5. T

    Ideal Classic FF

    No, just the pump and slight water circulating noise.
  6. T

    Ideal Classic FF

    Hi Kev, If you mean the three way valve, then that seems to work. All the stopcock valves are open. The boiler will fire up and run for a few minute, sufficient to warm the rads, the cold boiler return just starts to get lukewarm before the boiler then goes out but the fan continues to run...
  7. T

    Ideal Classic FF

    Ah, I see what you mean. Had this access screw off to turn the pump spindle and plenty of water came out - would this have been sufficient to bleed the pump?
  8. T

    Ideal Classic FF

    What a fast response! All rads have been bled and show water, including the refitted rads. Is there a special method to bleed the pump? The pump spindle turns freely and the pipes either side are hot. I see that another post had a similar problem traced to a siezed ball valve in the HE tank...
  9. T

    Ideal Classic FF

    After removing and re-fitting two downstairs radiators the boiler will light up and run for about 5 minutes, then the gas light goes out but the fan continues to run for a long time (over 15 minutes). The boiler can be switched off using the programer or room stat but will not re-light until...