  1. S

    Earthing in Spain

    I assume you have a poor neutral connection external to your property. Also you quite likely have a N - E fault internal to your property, do an insulation resistence test, if clear approach your supplier and ask him to rectify the external problem.
  2. S

    Earthing in Spain

    Neutral is obtained from the centre point on the transformer, centre point is also grounded to earth via a rod at source. Your reading at the property to earth I would expect to be in excess of 100 ohms, hence the differing potentials. Have you carried out a insulation resistence test on your...
  3. S

    Earthing in Spain

    A TT system relies on an RCD and an adequate return path to the transformer. A 60v reading between N & PE is not exceptional ,as they are at different potencials. I would advise you to loop test your PE and carry out an RCD test at the rated mA. Tripping during high winds is a problem in Spain...