    Help! Its cold ;)

    Kev, Dave many thanks for the replies. Kev many thanks for the manual. 3 Hours of troubleshooting by following the flow charts in the manual lead to the divertor valve. There was a tiny amount of corrosion on the mecahnisim that pushes against the microswitches. The mechanism would...
  2. S

    Help! Its cold ;)

    Kev recieved manual A OK. Seems very comprehensive. I will follow through some over the fault finding flowcharts over the next day or two. One thing I have now noticed is that the "Flow temperature meter" (meter next to pressure meter is always at 0. OR actually lying fully to the left . I have...
  3. S

    Help! Its cold ;)

    Apols. I just singed up and forgot to put my email in the profile ( stupid). Email is now in my profile. Many thanks, Simon
  4. S

    Help! Its cold ;)

    Hello, I have a Valiant VCW GB242 EH combi boiler. There is hot water but central heating only works for about 10 mins. I have watched it and what seems to happen is the radiators get hot and then the boiler clicks off. This seems fine thats what its supposed to do? BUt then when the temp of...