    Cable Size For Shower and Correction Factors For MCB's

    Yeah I didn't factor that in actually, I haven't seen it yet but it's probably around 9.5 @ 230. Thanks for pointing that out.
  2. D

    Cable Size For Shower and Correction Factors For MCB's

    You are probably right about over complicating. The installation method is actually C and I'm pretty certain it's fed from an RCD. Looks like I need to see if I can get a 45A MCB to make things a bit simpler based on ban-all-sheds reply too. Thanks for your input.
  3. D

    Cable Size For Shower and Correction Factors For MCB's

    Thanks for your input.
  4. D

    Cable Size For Shower and Correction Factors For MCB's

    Trying to work out cable size for a new shower and not sure what correction factors to apply to things these days. It's been a little while since I've done this. Here's what I have done so far. 10.5kW @ 230 = 45.65A = Ib Am I correct in saying that I can't apply diversity to this? The...