Search results

  1. D

    Immersion heater tripping probs!!

    The element is rated at 3kw from the metal cap, not sure of make, there's a wickes box with the old element in so if that's any help? The new stat is a bit tight to get pass to neutral terminal but does still slot in, i removed the flex clamp to show the connections, the wires are not on best...
  2. D

    Immersion heater tripping probs!!

    Here's a pic of the new stat. Think wiring is ok. Definitely MCB not RCD Tried the test flameport suggested, stat set to min, switched it on, it tripped the mcb, turned up the stat powered it back up switched it on, fine! Left it 30mins, switched off turned stat to min switched it back on...
  3. New Stat

    New Stat

  4. Immersion Heater

    Immersion Heater

    Immersion Heater
  5. D

    Immersion heater tripping probs!!

    Hi all, thanks for the replies, will get a photo uploaded today. The whole heater was changed 2 months ago as the old one had been in since the year dot and had simply given up. A plumber went round and changed it (new element and stat) in since tripped the MCB. This is where i went round to...
  6. D

    Immersion heater tripping probs!!

    brand new, apparently, been in 2 months and been on for about 5 hours on and off. More off than on!!
  7. D

    Immersion heater tripping probs!!

    Did try resistance test on element but didn't stabilize. So get the bloke in that put it in as with all that gunk round the nut i don't want touch it!!
  8. D

    Immersion heater tripping probs!!

    I have done resistance test on all points of the circuit and they where ok, on the element though the reading just kept slowly dropping could that be an indication that the element has blown? I read it should be around 17-20ohms i used a 2Mohms test...that's correct isn't it? Can i bypass the...
  9. D

    Immersion heater tripping probs!!

    I've had a multimeter on the wiring and that read sound, earth to the cylinder, neutral to correct peg, live in one side of the stat and out of the stat to other peg. Will the direction of power through the stat make a difference?
  10. D

    Immersion heater tripping probs!!

    The element is rated at 3KW so i assumed a 16amp MCB was right? It is a new Hager MCM and a new Backermatic stat plus a new double pole 20amp switch. Any Ideas?
  11. D

    Immersion heater tripping probs!!

    Hi all, new to this site, so any help will be very much appreciated. I have just replaced an immersion heater thermostat, (backermatic) but the MCB keeps tripping after a period of 1-2 hours. The old one was wired into the 32amp ring main circuit. I have since put it on it's own 16amp MCB and...