Search results

  1. J

    Gas boiler bypass query

    Yes, good point, I could dispense with the existing smart thermostat that's on the hallway wall and use just a smart TRV in the hallway radiator. This would give the same result, as you say. The smart wall thermostat (which I've used for over 2 years before acquiring any smart TRVs) would then...
  2. J

    Gas boiler bypass query

    I have the Tado system with all trvs being smart ones. The wall thermostat in the hallway is Tado's smart thermostat, but the smart TRV which is also in the hallway will not battle with the wall thermostat because I can select the temperature control in the hallway to be dictated by the wall...
  3. J

    Gas boiler bypass query

    This is exactly the current setup, which is unsatisfactory. If this radiator, which is in the hallway, has no smart TRV when all the other rooms have them then it will heat up when one or more of the other radiators is calling for heat, irrespective of the wall thermostat which is also in the...
  4. J

    Gas boiler bypass query

    Bypass pipe length would be about 1.5m long, and need to be routed through awkward angles and restricted space to connect flow to return, hence strong preference for the more flexible and space saving 15mm plastic pipe, rather than 22mm. As for whether I can still obtain the right flow or not...
  5. J

    Cast iron boiler descale - is this overkill?

    I'm aware that the copper flow pipe protrudes vertically downwards into the heat exchanger. So to minimise copper attack, to the point that is negligible, only 10% strength HCl would be used, cold, in the heat exchanger alone, and for only 45 mins, then the HE flushed thoroughly and neutralised...
  6. J

    Cast iron boiler descale - is this overkill?

    Thanks, Onetap. I'm about to start the descale later this week, and I'll report back on what I've done, and the outcome, soon after.
  7. J

    Cast iron boiler descale - is this overkill?

    Thank you Tony, that's a very helpful response.
  8. J

    Cast iron boiler descale - is this overkill?

    Tony, in my opening post I'm actually asking if my procedure involving these chemicals is overkill, so you're clearly saying "yes". The reason for wanting to use several chemicals in turn is because no one of them is good at dealing with all the types of unwanted deposit (limescale...
  9. J

    Cast iron boiler descale - is this overkill?

    Short term solution that only stores up problems for the future, surely? Washing up liquid contains 20% - 23% salt. Just what my steel radiators need! But thanks for the advice, serious or otherwise! Reminds me of cowboy car mechanics who quieten noisy gearboxes by adding sawdust to the oil.
  10. J

    Cast iron boiler descale - is this overkill?

    As far as I can tell, hydrochloric acid has no negative effects on rubber. Hydrochloric acid often comes in plastic (rubber family) containers, and H & S advise on using rubber gloves when handling this acid.
  11. J

    Cast iron boiler descale - is this overkill?

    I know there’s a lot of good advice on this forum on this topic, so I’m hoping for any useful comments on the plan below for descaling my cast iron boiler. Thanks in advance! The boiler is Potterton Netaheat Profile 50e, 25 yrs old and, for its first 24 years, never ever had any inhibitors...
  12. J

    Gassing in CH won't go away.

    Thanks for some helpful responses above. * Yes, sorry, I did mean to say Sulphamic (Sulfamic) Acid, and not sulphamite. * The pump has been raised to the highest of the 3 speeds several times in order to dislodge possible trapped air, and the normal speed is set at the middle one...
  13. J

    Gassing in CH won't go away.

    Thanks doitall, but that's just what was done during the flushing stage a few months ago. I must now presume there is residual magnetite etc that will always remain. Looks like Spiotech's air remover could be a last resort, but I'll wait a further couple of months.
  14. J

    Gassing in CH won't go away.

    The cylinder is copper, indirect, about 12 years old.
  15. J

    Gassing in CH won't go away.

    Perhaps I need to wait longer, into winter, for the system to get much more use. Also, the system volume is quite large, at 105 litres, when pressurised to 2 bar, so maybe I need to wait till mid-December and then re-assess
  16. J

    Gassing in CH won't go away.

    I'm trying to understand why I still have the problem 3 months on, which I expected to disappear after the first week or so when the fresh water was added.
  17. J

    Gassing in CH won't go away.

    The pressure rarely needs topping up, in spite of the regular bleeding. Only small amounts of gas are bled off. If I do need to top up it is via the mains water using the loop hose - undo the tap at each end, then close them. The system pressure was initially set at about 2 bar cold. That was...
  18. J

    Gassing in CH won't go away.

    I suppose my question relates to whether it is ever possible chemically to have clean tap water with the appropriate additives in the system that ensures no bubbles form at high temperatures like 85C (or perhaps even 90C if/when the time comes that the existing boiler is replaced by an Intergas...
  19. J

    Gassing in CH won't go away.

    JohnD, small quantities of black magnetite at Magnaclean, and yes reducing on every check, albeit slowly. I suppose the residual magnetite may be causing the gassing. Doesn't the X100 inhibitor stop this? Pressure relief valve not leaking.
  20. J

    Gassing in CH won't go away.

    It may not be hydrogen, but the point is it's unwanted gas. Hot pressure is 2 bar, cold is 1.8 bar. The intention is to stop the noisy bubbles forming in the first place, and not have to hear the bubbles causing noise on entry to the radiator(s). No leaking anywhere. Air seperators only...
Back
Top