  1. D

    halstead ace he 30 boiler no power

    Forgot to add, it sounds like the fan is constantly running
  2. D

    halstead ace he 30 boiler no power

    It's now turned on after a third fuse. I now have error code 7 which according to the manual is.... Fault/effect: defective/no flame Reason: missing or erroneous RPM signal Action: check fan, check mains fan lead and connector, check low voltage fan lead and connector, check PCB/x3...
  3. D

    halstead ace he 30 boiler no power

    Is there nothing else I can check myself first?
  4. D

    halstead ace he 30 boiler no power

    Found it. The fuse didn't look like it had blown but I changed it anyway. When I did this it tripped the electrics. Iturned them back on and checked the fuse again and it looks like this fuse may have blown too. Any ideas?
  5. D

    halstead ace he 30 boiler no power

    Would this be the fuse on the main electric board inside the unit?
  6. D

    halstead ace he 30 boiler no power

    I moved into my house about 2 years ago and have never had any problems with the boiler, however, this morning when i got up, i had no hot water or central heating. I had a look at the front of the boiler and it seems that there is no power as the display is completely blank. All the other...