    Warmflow boiler smoking

    Think about it the high limit stat was faulty which meant that boiler was at a higher than normal temp for prolonged periods so its possible for this to distort the baffel over a relatively short period of time. As i said the boiler was running for a good month or so after the service but as...
  2. M

    Warmflow boiler smoking

    So thanks for all ur help(not) but i got it sorted it was a baffle that was bent that was impinging on the flame that caused the problem i got a replacement and all is going well now i also changed the high limit stat which was causing the over heating. I am pretty annoyed at all the...
  3. M

    Warmflow boiler smoking

    I am at my wits end my warmflow 50/70 whitebird boiler and it has been smoking recently its been services and the jet has been changed i found that the air intake pipe is also the exhaust pipe and the reducer had melted so i thought that the burner was drawing in more air than needed so i...