  1. D

    lights on a ring circuit

    Can a lighting circuit be wired in a ring type circuit? If so, is there a maximum amount off load the circuit can take? :?
  2. D

    how many sockets on a ring main?

    I've been told by an electrician many years ago, that you can have as many 13amp sockets on a ring main as you want, providing each sockets load does not exceed 13amps. Is this still the case?
  3. D

    cross bonding confusion

    if my property has a 4mm continous earth cross bonding my water pipes to the boiler and water stop cock, do i need to return the earth back to the consumer unit(like a ring main)? :?
  4. D

    earth cable diameter oa a 100amp tns

    I was hoping someone would clarify the requirements for the minimum diameter (on a 100 amp tn-s) earth cable. The cable from the incoming supply to the consumer unit is 16mm.The earth cable from the c.u. to the ring main sockets, lights, shower, cooker etc is only 10mm, is this acceptable?
  5. D

    TN-S mains supply

    Hi guys, I have a TN-S mains supply with a 100 amp fuse. I was wondering if anyone could tell me what size diameter earth cable and tails should be fitted. cheers Damian :)
  6. D

    rewire house

    hi guys, I had a sparky inspect my wiring and he said I needed the following, Description of non-conformaties to current IEE Wiring regulations, on visual inspection. 1, Equipotential bonding to water to small, also in wrong place. 2, No RCD to ground sockets or to shower...