  1. L

    Boiler Frost Stat

    Problem was loose connection to pump.
  2. L

    Boiler circulating pump stays on

    Problem fixed, there are two connections to pump and one was loose, this meant pump came on but didn't go off. Thanks all.
  3. L

    Boiler circulating pump stays on

    Looks like they are connected in series, so both are on for pump or one is off for no pump
  4. L

    Boiler circulating pump stays on

    Pipe stat is connected to frost stat - so have disconnected both.
  5. L

    Boiler circulating pump stays on

    Disconnected frost stat and noise persists.
  6. L

    Boiler circulating pump stays on

    Frost stat is right next to boiler, with a pipestat on the ch return flow, all is pretty well insulated and not far from the boiler.
  7. L

    Boiler circulating pump stays on

    As the problem does not arise during the day, mr WB wouldn't of experienced it.
  8. L

    Boiler circulating pump stays on

    Boiler is in the attic, it's a bungalow
  9. L

    Boiler circulating pump stays on

    Boiler still under warranty, WB man came round to look at. External frost stat doesn't seem to be the problem as it is coming on when it is still warm, and if I turn boiler off and leave for a while and restart the pump doesn't come on again, even though the temperature is just as cold or even...
  10. L

    Boiler circulating pump stays on

    Thanks for the reply, it only seems to not be able to turn off in the evening. I don't know why it starts, the only thing I can think of is the regular pump run to stop seizure, but don't know when this is set to come on so can't confirm. Running Ch and water does not result in pump staying...
  11. L

    Boiler circulating pump stays on

    Have a worcester Bosch 30 cdi. Circulating pump stays on in the evening and would stay on throughout the night if I didn't turn off boiler. had someone round from WB, and wiring is ok. Though he didn't think there was a need for a frost stat given that piping was not that long and far from...
  12. L

    Boiler Frost Stat

    had someone round from WB, and wiring is ok. Though he didn't think there was a need for a frost stat given that piping was not that long and far from the boiler. Apparently a frost stat runs the circulating pump only on this model and that would kick in the frost stat in the boiler etc etc...
  13. L

    Boiler Frost Stat

    So wiring looks to be at fault. Can anyone explain why the pump comes on but not the gas lighting ?
  14. L

    Boiler Frost Stat

    Its located in the attic - so there is an external frost stat and pipe stat as I believe that boiler frost protection is for internal pipework only. If it were only the external frost stat I feel pretty confident i can change this - but not the wiring into the boiler (though i cant think that...
  15. L

    Boiler Frost Stat

    Boiler is a worcester bosch 30cdi combi - i believe that there is also on board frost protection from the gumpf that cam with boiler.
  16. L

    Boiler Frost Stat

    I have a problem with me boiler. It is reasonably new and work fine when hot water and central heating are operated but the problem seems to be when the Frost Stat is operated. when I set this to a temperature above the ambient temperature and set the temp on the pipe stat above that then...