  1. M

    Blocked cold feed and leak

    I bought a new pump today (installed so the shaft is horizontal, thanks for the heads up) and it's working like a dream, significantly less noisy than the old pump. So all sorted now, thanks again!
  2. M

    Blocked cold feed and leak

    Thanks for copying that Blagard, I struggled to find the manual too. Yes looks like it was the pump that had gone after all. When I start it manually it works great. Wish I'd properly tried this first time... I thought it was working as I could feel it vibrate and rumble when it was on, the...
  3. M

    Blocked cold feed and leak

    I've replaced the air separator but (unfortunately?) it was actually in pretty good nick magnetite-wise. So sadly I still have the situation where the boiler starts up fine but quickly boiling water flows over into the F&E tank through the vent and it sounds as though air is possibly...
  4. M

    Blocked cold feed and leak

    Hi, thanks for your helpful responses, I've ordered in a new air separator and plan to replace it - probably storing up trouble for myself otherwise as you say. I was a little confused why the magnet wouldn't stick around the air separator inlet if it was blocked, which I think it must be, but...
  5. M

    Blocked cold feed and leak

    Hi, I recently moved house and a few days ago my central heating broke down. Even since I moved in the system was quite noisy, but it had been getting louder over the last few weeks until two days ago when it would start up but after the boiler had fired up it would cut out after more than only...
  6. SHOT2.jpg

    SHOT2.jpg

    hairline crack
  7. pump and pipework

    pump and pipework

  8. leak

    leak

Back