  1. S

    Water, but no heating. Possible 3PV?

    Thank Christ for that. I bet that was like pulling teeth for you eh Freddo?
  2. S

    Water, but no heating. Possible 3PV?

    Yes, terminal 1 (I was going off terminal 4 of 7). I just wired terminal 1 to terminal 4 and fired it up, boiler kicked in when heating demanded. The voltages from earlier i tried again with both stats set to max: HW W=0v, G=0v, O=240v HW/CH W=240v, G=73v, O=240v CH W=240v, G=73v, O=42v If...
  3. S

    Water, but no heating. Possible 3PV?

    That sounds like my kind of fault finding........ I'll try it later when the kids aren't wrapped around my ankles. I was thinking of splitting the unit apart and sticking the unit back in place by the pins so I can get my probe down the back of it while it's still on. On a side note, I checked...
  4. S

    Water, but no heating. Possible 3PV?

    Freddo, I've just re-read this thread and realised how novice I sound. Now having more than a hunch of how the system is supposed to operate, it is clear that the programmer isn't playing ball so I'm going to check each terminal properly to confirm before I splash out my hard earned money on...
  5. S

    Water, but no heating. Possible 3PV?

    You're a star Freddo, but I'll to give it a shot in the morning as the nipper is in bed and the airing cupboard is in her bedroom. From memory of fiddling around with it earlier, I DID try that and the valve didn't move. It would only move with HW off. As soon as HW is switched on, the valve...
  6. S

    Water, but no heating. Possible 3PV?

    Update: Just had it set to CH only, valve motored and made S1, I made S2 with a non metallic pokey thing, a relay inside the valve head clicked (A LOT) and the boiler fired up until I let go of S2. I've checked and checked again for loose wires and I'm certain the programmer (Honeywell...
  7. S

    Water, but no heating. Possible 3PV?

    Well.......that's just pi$$ed on my chips. I was certain it was the valve head as S2 isn't making when it motors over
  8. S

    Water, but no heating. Possible 3PV?

    HW off, CH on; White=240v Grey=around 70v Orange=around 40v I'm really tempted to try and make S2 with something non conductive and see if the boiler fires up
  9. S

    Water, but no heating. Possible 3PV?

    Ahhhhhh. That makes more sense. Very helpful diagram by the way Freddo. When I took the cover off and watched it motor over, everytime it would only make contact with S1. The only time when it made S2 is when I motored it by hand but then it would bounce back as the lever rested in the gate...
  10. S

    Water, but no heating. Possible 3PV?

    Hi, I've have a question that might help me clarify what the fudge is going on with my system, in particular a Honeywell 3PV: When I switch DHW off and turn the stat up for CH the 3PV motors open but the boiler isn't firing up. I've checked for 240v on terminal 7 from the orange wire and I...