    TRAINCO OIL BURNER LOCK OUT

    All fixed. I was going to change the solenoid valve, but found that I could buy a pump complete with valve for only £15 extra. I had also noticed either the pump or blower motor were noisy, so bought a pump. Anyway fitted new pump - nice and quite and cured problem. Set pressure and CO2 all...
  2. B

    TRAINCO OIL BURNER LOCK OUT

    OK, found that coil. A tad difficult to get to due to the boiler being up against a LH wall, and adjacent to wall cupboard, I have the take the burner out to get to it. It has a resistance of 2.07 ohms. Also, I noticed that the burner shuts down, then the fan runs for a few secs 10 - 15 maybe...
  3. B

    TRAINCO OIL BURNER LOCK OUT

    Thanks for the very swift reply Oilhead I have a multi meter so that sounds like a plan. Do I need to disconnect the solenoid before measuring? If so how?
  4. B

    TRAINCO OIL BURNER LOCK OUT

    HELP!! I have a Trainco Eurostar WM 50/70 boiler. That fires up ok, then locks out after about 10 - 15 mins. I thought a service was due so I: Replaced the burner jet Replaced the photo -cell Cleaned the baffles Checked the electrode positions But it still locks out after 10- 15...