    Vaillant Ecotec Plus - Pump overrun when restarting

    Hi All Just to give you an update. I had an engineer coming last week. He came up with pretty much the same diagnostic - "system working properly". I now have the d.0 at 10 and temperature at 65 degrees. With these settings it almost works fine. Sometimes the boiler switches off a bit more...
  2. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Sorry for that. When doing the video on the first post the d.0 was 25. I will try to reduce tomorrow to see how it goes.
  3. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Thanks. Pump is already on III. The d.0 setting is something I had already changed previously. It improves things a lot but doesn't remove the pump overrun issue completely. Is there a way I can check the amount of water that gets into the boiler to see if the pump doesn't pump enough? Let's...
  4. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Hi I have 12 radiators (some being quite small) and a water tank. But the thing is I still get the same bug when only the HW is switched on on (ie flow only goes to 5 radiators plus tank). Actually the bug is even more pronounced when only the HW is on. The pump is a alpha2L 15-50 130. House is...
  5. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Thanks I checked with 65 and still getting the bug. I have an engineer coming on Friday. Will let you know what he thinks.
  6. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Thanks again for all your responses. The way our boiler is installed, all the hot water (kitchen + bathroom + everywhere else) comes from the water tank. I'm not 100% sure about the model. I think it's 428 but I will have to double check this evening.
  7. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Sorry for the confusion. On our specific installation the boiler doesn't act as a combi. Only the second temperature knob gets used as far as I understand. I will try heating at 66-70 to see if it makes a difference. But thought it was more energy efficient to stay on a low temperature which is...
  8. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    No 75 fault. All I get is S.7 pump overrun. When I increase the temp at the control knob I can see the display changing and then the boiler would react by increasing its temperature. However if I reduce the temp on the knob then the boiler would go into pump overrun and I would have to let it...
  9. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Thanks picasso. Whats the best way to check / clean / change the canoe filter? Does that come with the heat exchanger?
  10. T

    Vaillant Ecotec Plus - Pump overrun when restarting

    Hello everyone and thanks in advance for any idea you may have on my problem. Here is the situation. My boiler is a vaillant ecotec plus (combi) connected to a a series of radiators and a water tank with a "Y" scheme. Boiler works fine. The only problem is it wont "restart" while it is still...