  1. A

    Chaff 100

    Thanks guys it was CH Flow switch/ Throttle. How do you do a fan pressure test ive found some data in the manufac instructions but not sure is a electronic manometer test? Be interested to know as new to game Thanks
  2. A

    Chaff 100

    Yes gordongas its a calydra 100 thanks will check them
  3. A

    Chaff 100

    Got A problem boiler not sparking changed air pressure switch no :( joy. Fan is ok dont think pump running any ideas
  4. A

    BRITTONY SE80 POWER PROBLEM

    gOT a BRITTONY SE80 EVRY TIME IT FIRES UP IT TRIPS RING MAIN. RING MAIN OK TESTED FOR INSULATION, POLARITY ETC. ANY TIPS ON WHERE TO START ON BOILER RECENTLY HAD A NEW PCB. OBVIOUS POWER PROBLEM SOMEWHERE NOT SURE WHERE TO START. PCB :cry: 2A FUSES OK NEVER BLOWN
  5. A

    chaff brittony 2t

    No correct Diaphragm, I got a Second- Hand water section of a scrapped Brittony 2T and replaced along with the Diaphragm and it worked ok i think looking at the old 1 it was slighty distorted and wasn't sitting quite true. All ok now and it fired up great guns and flow and temp ok. Above all i...
  6. A

    chaff brittony 2t

    I put a second-hand Water section on the damn thing and it worked. Your right about the Diaphragms being very similar for the Celtic and The Brittony 2T. Thanks All :D
  7. A

    chaff brittony 2t

    No but what made me wonder was that i remember a gasket being on 1 i changed a while ago. i've put a new diaphragm in the right way but water keeps seeping out all round the sides of the housing its the correct diaphragm and the fitting is secure i.e all six screws are tight but why is it...
  8. A

    chaff brittony 2t

    replaced a diaphgram in a brittony 2t is it supposed to have a gasket as well as its now leaking. It has a water section repair kit in place and the body is brass. But didn\\\'t seem to have a gasket when it came off! Just a worn rubber diaphgram
  9. A

    Chaff SE80

    it was the pcb
  10. A

    Chaff SE80

    Attended a Breakdown of a Chaff SE80 Symptoms:Locking Out No sparking. Cleaned Fan up cleaned all terminals around APS as plastering recently carried out, carried out a full clean up got going ok CH & DHW Temps ok left running for a couple of hours no problem. Been back 3 times same problem but...
  11. A

    boiler tripping rcd

    Could be a faulty RCD Get it checked by a Part P Qualified person or the system checked on a mega or a Fluke.
  12. A

    Upstairs Radiators

    Sounds like trapped air lock in system. Try draining and refilling to try and shift it or cranking open rads on the big nut ends as oppossed to the bleed screws, sometimes shifts an air lock. Also vent pump.
  13. A

    noisy boiler

    What isolating valve???? As i said flow rate and water temp ok. There is no isolating valve on hot water outlet. Cold Water inlet opened and stop cock nothing restricting flow to appliance.
  14. A

    noisy boiler

    Do you mean the air release valve ?
  15. A

    Whining combi-boiler

    Could be a blockage i.e water is not getting across the heat exchanger quick enough. Have you checked the inlet filters for debris??
  16. A

    noisy boiler

    got a Worcester 24CDI CH OK When in DHW mode boiler makes a banging noise suspect air, but flow rate & Temp ok, pressure gauge fluctuates wildly
  17. A

    noisy boiler noise in DHW mode

    Hi All, got a Problem with a Worcester 24cdi every time i call for HW a loud banging noise coming from boiler. i,m thinking air! CH OK No banging. or do you think blockage in Sec Heat Exchanger :?