Search results

  1. B

    Armoured cable from CU to 13amp socket in garden

    Cheers for your positive responses. I have put feed from C/U on non RCD protected side of C/U fed through the wall directly to an RCD spur that sits on the outside wall of the house. I thus achieve protection tof he internal "feed" portion of the circuit as it is enclosed in the wall &...
  2. B

    Armoured cable from CU to 13amp socket in garden

    Maybe read my post again & think about it. The cable is protected to a degree. But were is the line drawn ultimately if it suffers a break, short etc including the external junction box. For instance if this box recieves a blow & the inner wires are exposed. If these were not protected...
  3. B

    Armoured cable from CU to 13amp socket in garden

    Yes the system is TN-C-S and it is earthed from the supply end. Ok. I will move it to the non-rcd protected side & re-test at 1/2, 1 & 5 . Thanks
  4. B

    Armoured cable from CU to 13amp socket in garden

    I have installed an armoured cable in a parking area to power a 13amp socket with a protected 3amp spur off a radial circuit to power a bulkhead security light with PIR. The 13amp accessory socket is rated IP56 and protected by an inbuilt 30mA RCD. The armoured cable from the house is...
Back
Top