    Programmer / Timer replacement on an old boiler . Pump over run needed

    lol ... it shows that your grey matter is in good nick heatservice. I guess once it becomes 2nd nature, it will stay indefinitely ... it's always good fun to solve problems or work around them. when it works it feels good. Then move on to the next, whatever it may be, but only quite a safe...
  2. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Opps, big thanks of course to heatservice. but thank you all the same .. this has been a very interesting & educational discussion. it has helped me understand more by focusing on the principles, and I was able to resolve the pump overrun by using the existing old timer with new timer, I...
  3. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    your microswitch overrun diagram is spot on. the unit is a clever microswitch adaptation with parts not exceeding a few quid to manufacture. I agree with the versatility, hence i quite favour this method . (good to know the 1012 can fit diff. pipe sizes) thanks!!
  4. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Stem: I quite favour your suggestion of Honeywell 641B 1012 pipe stat. not now, but only when the old timer microswitch gives up. Just connect the pipe stat to the pump totally independently, controlled by the boiler out temperature. with the Timer just controlling the boiler alone. was that...
  5. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    found this interesting image of pump overrun solution? with Honeywell pipe stat
  6. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Thanks to all - my current issue is resolved for now .. ( but still exploring .. ) Heatservice as you were the first to kindly mention Pipe stat what is your ( or anyone's ) opinion on this (ebay) interesting stat... it claims good for 10-90deg C (As this is a cylinder stat I am puzzling how to...
  7. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    using existing configuration with new timer will be installed after next visit to shops to grab some crimp connectors :)
  8. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Thats what I am doing right now ... keeping the old timer as is. the boiler L & N redirected to new boiler + mains supply L & N shared between the 2. using the old as pump over run. new timer just to serve the boiler. Mounting new timer externally is much better and very convenient. the new 424...
  9. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    GAS VALVE to Programmer Solenoid terminal: I am not sure.. but I have a feeling that this red wire from the gas value maybe a DC current instead of AC ? the ceramic plate has a grey metalic conductor strip ( see image above) that heats up the stat plate next to it... Or probably the wire...
  10. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Stem: yes the red wire from gas valve is connected to the existing timer terminal (2) solenoid. which then, from this terminal, a white wire is wired to the 2nd terminal of microswitch and relayed to ceramic heating place. I have linked the actual positions with green lines between the drawing...
  11. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Ifcpat I am interested in buying the elite 50 converter.. I couldnt quite grasp the whole process. can you give me baby steps illustration so my slow mind could comprehend :) say how the "="s correspond with converter terminals etc...
  12. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Oh... thanks .. LOL I didnt realise it was a full timer .. ServoWarm ( "I think") was taken over probably by Homeserve, or Glow Warm? so is a gonner so I doubt I can find one. So it's likely be back to the drawing board. I could remove the simple overrun unit and transfer it to the new 424...
  13. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    thanks Ifcpat... - studying the terminals - 1 - 7 from top:, if I elaborate as I see it ( I think) I would like to use this merely as a pump over run relay. (the boiler will be switched from timer so can I just ignore 5-7)?) 1) L out to pump 2) - 3) permanent L/N from mains ( or timer...
  14. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Thank you ifcpat for posting the photos.. would you be able to give makes models etc of the necessary units/devices to help me work out or reproduce your suggested pump overrun solution?
  15. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    ------------------------------------------------------------------------------------------------ Thanks Stem: I have just ordered the old "standard"( no pump overrun) discontinued new horstmann 424 Emerald . As a "temporary" measure ONLY ( until I sort out a preferred pump overrun option). The...
  16. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    -Thanks Stem I am absorbing this gradually...Honeywell L641B 1012 pipe stat to be mounted on the hot out pipe (Y) -Schneider Electric OFF Delay Single Timer Relay, Screw, 0.1 s → 100 h, SPDT, 2 Contacts, SPDT -this seems good but I dont understand how it fits in... it looks interesting.. do...
  17. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    Stem/heat service - this makes sense ... do you have link to a specific pipe stat model I can look at to follow up this connection? thanks
  18. M

    Programmer / Timer replacement on an old boiler . Pump over run needed

    No this is just like any normal mounted boiler. with timer and pump at the bottom. This ebay unit is the same 424 Emerald model but it has no pump overrun. This boiler has a bespoke 424 emerald , same design but they added a clever pump over run with microswitch. So my replacement will need...