  1. Bence

    Drayton Wiser hub does not close TRVs

    Hi, I did manage to solve it. It turned out that the firmware of the HUB was old and this was the reason why it was unable to control the TRVs. You cannot update the firmware but the Drayton support team can do it for you remotely. I would definitely write them and ask them to check the...
  2. Bence

    Drayton Wiser hub does not close TRVs

    No noise can be heard. The actuator only moves when I start the calibration process. Then I can hear the sound and it is moving in and out. If it is attached to the radiator, there is no noise, nor actuator movement, even if I turn of the zone in the app. This applies to all 6 radiator thermostats.
  3. Bence

    Drayton Wiser hub does not close TRVs

    I did not change anything in the plumbing, so I'm using the existing valves but with Wiser TRVs.
  4. Bence

    Drayton Wiser hub does not close TRVs

    Tried it and nothing changed. It seems the hub does not want to open or close the valves. Strange because the connection between them is ok.
  5. Bence

    Drayton Wiser hub does not close TRVs

    Currently waiting for their reply, but they can be very slow. Setting up the system with their help took almost two weeks.
  6. Bence

    Drayton Wiser hub does not close TRVs

    Hi Guys, I'm trying to install and set up a Drayton Wiser kit 1 with 6 radiator thermostats for several days. The heathub turns on the boiler and starts heating, BUT hot water is constantly circulating in all of the radiators. For example I want to heat the kitchen up to 22 Celsius from 18...