  1. Dicksonkj

    Boiler overheating

    Thanks again, that all makes sense.
  2. Dicksonkj

    Boiler overheating

    Thanks DP that’s really helpful, the pump is not currently wired to the boiler so I will take a look at that. I’ve adjusted the bypass valve and that’s reduced the return temp to the boiler. I’ve also noticed that when the boiler stat is showing 78degrees I’m only getting 63 degrees at the...
  3. Dicksonkj

    Boiler overheating

    Thanks, it runs pretty quiet but I will take a look at that too.
  4. Dicksonkj

    Boiler overheating

    Ok thanks, just wondered if the bypass being open all of the time would make the boiler less efficient as it might stop it condensing?
  5. Dicksonkj

    Boiler overheating

    Thanks for your help. So would 2 metres equate to the number 2 setting on the bypass valve?
  6. Dicksonkj

    Boiler overheating

    Thank you for the link that’s really useful and I will give that a go. Would I be right in thinking that with the valve fully open I’m loosing some heat to the rads and also that the water going back to the boiler via the valve will make it too hot for the boiler to condense?
  7. Dicksonkj

    Boiler overheating

    Hi, wonder if anyone can help with the following issue. I have a Worcester Bosch CDI 30 Greenstar boiler with a DAB 40-70/130 pump, 2 times 2 port valves one ch, one dhw. When the room stat reaches temperature the boiler temperature increases rapidly and can display U9 value which I believe is...