  1. C

    Balancing a system with lock shield on outlet

    Acova from screwfix, of difference sizes, 3 columns. Can’t seem to put a link.
  2. C

    Balancing a system with lock shield on outlet

    John - got any ideas?! Still suffering over here…
  3. C

    Balancing a system with lock shield on outlet

    (instruction manual says:) VERY IMPORTANT: PLEASE NOTE: WHEN CONNECTING THE PIPEWORK TO THE RADIATOR, THE WATER MUST ENTER THE RADIATOR AT THE BOTTOM CORNER DIAGONALLY OPPOSITE THE AIR VENT AND EXIT AT THE BOTTOM CORNER BELOW THE AIR VENT.
  4. C

    Balancing a system with lock shield on outlet

    Ok, the instructions state the bleed valve must be the opposite side to the inlet. And the valve is fixed, as is the blank, so must be correct way round.
  5. C

    Balancing a system with lock shield on outlet

    Yes, they are all now plumbed in with the inlet opposite corner to bleed valve. They also have simply valves like you’d fit to towel rails as I was told TRVs could be problematic. So they’ve all been drained, off the wall, and dumped out a lot of clear water so I really don’t think they’re blocked.
  6. C

    Balancing a system with lock shield on outlet

    I can try that, but the downstairs radiators aren’t super hot anyway… so I am guessing there is a big problem here. The bigger column rads aren’t getting hot to touch, just warm.
  7. C

    Balancing a system with lock shield on outlet

    How do I find out the pump speed?
  8. C

    Balancing a system with lock shield on outlet

    So now the lockshields are closed everywhere else, the downstairs rads are warming up. The inlets are very hot, rads are slowing getting warm, outlets less so but they are column radiators so I guess it takes a while?
  9. C

    Balancing a system with lock shield on outlet

    Not sure! “Designed and manufactured by Vaillant, the ecoTEC Plus 637 is a condensing system gas boiler that would suit the heating and hot water demand of larger homes.”
  10. C

    Balancing a system with lock shield on outlet

    Not yet… I will do that and let you know.
  11. C

    Balancing a system with lock shield on outlet

    Well all the lockshields upstairs are now a quarter turn open and TRVs fully open. All rads upstairs are hot. Everything downstairs is stone cold. I have a modern valiant boiler and 8 rads across first floor and loft; 3 towel rails (which I’ve not got on too hot) and 5 column rads downstairs...
  12. C

    Balancing a system with lock shield on outlet

    Ok, thanks. So if the lockshield is red hot, the radiator is hot, but the trv is only lukewarm, what should I do? The radiator is hot after all… but does that mean the system won’t be properly balanced?
  13. C

    Balancing a system with lock shield on outlet

    I need some help, having real difficulty balancing my radiators. Got modern slim rads upstairs, columns downstairs. Downstairs the rads are all on the right way. Upstairs, TRVs and lock shields are mostly on the wrong way. I understand they are bidirectional, but when trying to balance the...