  1. J

    honeywell cm927 to valliant 937

    Just to update the post.. got my boiler guy out and he stripped out the wireless Honeywell unit and replaced it with a standard wired thermostat.. Unfortunately same issues, the heating is behaving erratically again another night of no heat, in the morning it randomly kicked in and has been fine...
  2. J

    honeywell cm927 to valliant 937

    might leave that to the expert.. I'm not 100% comfortable playing around with the electrics.. but will remember and suggest it to my guy.. thanks for your input thus far it's been helpful
  3. J

    honeywell cm927 to valliant 937

    I've got a guy coming over tomorrow to have a look.. He will remove the honeywell since I'm considering changing it anyway to a Nest. He'll temporarily fix a manual wired stat as an interim and we'll check all the connection and see what happens from then onwards.. Thanks for your input its...
  4. J

    honeywell cm927 to valliant 937

    I'll have a chat someone i know who is gas safe and fits Valliants and take it from there if no luck I'll be sure to come back on here.. thanking you kindly
  5. J

    honeywell cm927 to valliant 937

    Would a PCB fault not at least show as a F code. That is the thing that is bugging me most is that I have no error codes to work with.. I will have to get a boiler guy down.. just don't want someone to come over with a call out charge and not find anything wrong with the set up.. The fault is...
  6. J

    honeywell cm927 to valliant 937

    Which it wasn't doing so clearly something not right there....I wonder...
  7. J

    honeywell cm927 to valliant 937

    What you were saying is that by moving the wires over it should have kept the heating on constantly bypassing the thermostat.. Which it wasn't doing.. it was behaving the same way as before the wire change. still giving S.30 code. So wouldn't that indicate a stat receiver problem? not sure now
  8. J

    honeywell cm927 to valliant 937

    Yep i think i did reply to your message. I moved the Wire from B and put it in A, and rebooted the boiler and it was exactly the same no change.. it didn't make any difference at all.. Was still showing the S.30 code. however randomly pre wire change it was exhibiting random status code...
  9. J

    honeywell cm927 to valliant 937

    I'll have to do some wire trailing and figure this out and come back to you guys... It's just odd that it seems to work at random times.. Like for instance.. All night it was perfectly fine and i had good heat.. then randomly about 5am the heating had gone.. nothing consistent about it as I...
  10. J

    honeywell cm927 to valliant 937

    okay will do some checking thanks
  11. J

    honeywell cm927 to valliant 937

    I have a multimeter and voltage tester somewhere yes..
  12. J

    honeywell cm927 to valliant 937

    As promised here is another angle with the wires more obvious let me know your thoughts: x2 Brown wires in the first port on the left x1 Blue to to RT x2 Brown to L x1 Blue to N x1 Green/Yellow to The right most port
  13. J

    honeywell cm927 to valliant 937

    I moved the wire from point B to A on the stat receiver and powered up the boiler and it made no difference Still showing the S.30 status message.. Does that indicate a dodgy receiver?
  14. J

    honeywell cm927 to valliant 937

    no work carried out recently to be honest both flow and return values are as they have been nothing changed there.. I dont use Zone valves. Each Rad has a thermostat but again nothing changed there.. Not sure about the 24v link and what I'm looking for there but will have to investigate thanks
  15. J

    honeywell cm927 to valliant 937

    I promise to upload a better picture shortly when I get home from work.. In the mean time i took a recording of the boiler behaviour via Live Data.. I've added 2 videos if you guys can have a look which might identify what the issue could be. I'm starting to think maybe it's not the thermostat...
  16. J

    honeywell cm927 to valliant 937

    Might be a good test just to get the boiler working and seeing if i get the status message or not. I'll move the B wire on the stat receiver to A and see if that kicks the heating in
  17. J

    honeywell cm927 to valliant 937

    maybe time to upgrade to a Nest.. just a shame I can't pinpoint if it is the stat that is causing the issue.. I might have to see if i can disconnect it completely and see what the boiler does
  18. J

    honeywell cm927 to valliant 937

    The stat is on a stand mostly sits in the bedroom away from radiators. its a portable stat so can take it to any room.. but mostly in the bedroom where it has sat for the last 5 years and has been working fine up until now.. I can force the boiler in to chimney sweep mode and the heating does...
  19. J

    honeywell cm927 to valliant 937

    fair enough thanks for your input definitely something dodgy going on as it shouldn't be clicking on and off constantly every second for a few minutes then go off completely then back on randomly.. however from the looks of things the thermostat and receiver seem to be lighting the usual lights...
  20. J

    honeywell cm927 to valliant 937

    Hi There - I've been in my house a few years and recently noticed issues with my heating constantly going off and on, could be fine for a week but then for the next few days it clicks on and off randomly, sometimes giving me heat for 30 minutes sometimes 5 minutes, nothing consistent. When its...