  1. C

    RCD Trip

    It's been doing it last few weeks - the new circuit only got installed recently
  2. C

    RCD Trip

    Ok, I think iv noticed the issue. My CU is has 2 RCD's protecting 6 circuits each. The circuit that kept blowing: the neutral wires were wired Into the neutral bar for the 2nd Set of RCD's (hope that makes sense). This would explain why both RCD's were tripping.
  3. C

    RCD Trip

    That's a very good point! Iv just tried it all again. The socket tester itself didn't trip the RCD's. But when I plugged in an appliance and switched it on - the RCD tripped and the internal Fuse on the socket tester is now blown
  4. C

    RCD Trip

    I bought a socket tester. It shows no faults on any of the sockets. If I turn the MCBO on, and leave the 'ring' alone, the RCD does not trip. If I turn on any of the switches (nothing is plugged in), the RCD Trips.
  5. C

    RCD Trip

    32amp Ring Circuit. Even with nothing plugged in, when a socket is switched on - the RCD trips.