  1. B

    Is my pipe/rad layout poorly designed?

    The power flush on Monday morning did it. It wasn't the rads, as after being on for 5 hours with downstairs rads turned off, the upstairs rads would eventually get hot top to bottom. So there was clearly a partial blockage somewhere in the upstairs pipework, or possibly in the short section...
  2. B

    Is my pipe/rad layout poorly designed?

    So there "was" a bypass. I've had the floorboards up and can clearly see the pipes for a bypass, but a previous plumber/gas engineer has squashed the feed pipe flat just after it tees into the radiator to prevent flow to the bypass. A brief test this morning shows that it hasn't stopped the...
  3. B

    Is my pipe/rad layout poorly designed?

    Well that's beyond my knowledge for sure. I can only find out if there is a bypass, and the heating engineer can take it from there. He's been fitting baxis for many years, so may know if there's a motorised valve etc. I will ask him when he gets back on Monday.
  4. B

    Is my pipe/rad layout poorly designed?

    I'll be looking into that bypass asap, as that could easily be the answer.
  5. B

    Is my pipe/rad layout poorly designed?

    Not sure what ufh is, but possibly under floor heating? If so, I don't have that. Although all of the downstairs piping does run under the floor in a well ventilated void, and no insulation on the pipes. I would assume a decent loss there. A mammoth and destructive task to retrofit insulation...
  6. B

    Is my pipe/rad layout poorly designed?

    I don't know the actual temperature, but after 15 to 30 mins of running, the return pipe is hot enough that the boiler either slows down or turns off. I don't know if the boiler modulates at this point, or just turns off for a while. Not sure how "clever" it is. At this point, the downstairs...
  7. B

    Is my pipe/rad layout poorly designed?

    From original post: "The boiler is a recent Baxi platinum 40kw, and the system had a chemical flush when fitted, but not a power flush." It's not the balancing. I shut all downstairs rads off completely, and the rads were still very slow (45 mins) to get hot upstairs, and they were already warm...
  8. B

    Is my pipe/rad layout poorly designed?

    19 rads in total. Boiler brand new. Yes, large magna clean filter on return. Filter is clean. Not sure about a mesh filter. Will check tomorrow. Thanks.
  9. B

    Is my pipe/rad layout poorly designed?

    "Carry on with the balancing." All downstairs rads are set between 1/8 and 1/4 turn on the lockshields. Hard to turn them down much more! "Is this a one pipe system" No, all radiators are on a feed and return system, so there are 2 pipes going around the whole system. I'm now looking into the...
  10. B

    Is my pipe/rad layout poorly designed?

    Hi. Hoping someone can advise. My downstairs CH system is on 3 loops. First loop 3 rads, Second loop 7 rads, Third loop 3 rads. All loops return via the main 22mm pipe to the boiler. However, the second loop also feeds 6 upstairs rads, making a total of 13 rads on that loop. The upstairs rads...